Siemens 6ED1050-1AA00-0BE8 User Manual

Page of 372
 
LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 04/2011, A5E03556174-01 
175
 
4.4.7 
Asynchronous pulse generator 
Short description 
The output pulse shape can be modified by reconfiguring the pulse/pause ratio.      
 
Symbol in LOGO! 
Wiring 
Description 
Input En 
You can use input EN to set and reset the 
asynchronous pulse generator. 
Input INV 
Input INV can be used to invert the output signal of 
the active asynchronous pulse generator. 
Parameter 
You can configure the pulse width T
H
 and the 
interpulse width T
L
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
4
(Q
,QY
3DU
 
Output Q 
Q is set and reset cyclically according to the 
pulse/pause ratio T
H
 and T
L
Parameters TH and TL 
Note the information on parameter T in topic Time response (Page 151)  
The pulse width TH and the interpulse width TL can be provided by the actual value of 
another already-programmed function. You can use the actual values of the following 
functions:  
●  Analog comparator (Page 218) (actual value Ax – Ay) 
●  Analog threshold trigger (Page 213) (actual value Ax) 
●  Analog amplifier (Page 226) (actual value Ax) 
●  Analog multiplexer (Pag248) (actual value AQ) 
●  Analog ramp (Page 251) (actual value AQ) 
●  Mathematic instruction (Page 265) (actual value AQ) 
●  PI controller (Page 256) (actual value AQ) 
●  Up/down counter (Pag201) (actual value Cnt) 
 
If your LOGO! is a LOGO! 0BA7, you can additionally use the actual values of the following 
functions: 
●  Analog filter (0BA7 only) (Page 271) (actual value AQ) 
●  Average value (0BA7 only) (Page 276) (actual value AQ) 
●  Max/Min (0BA7 only) (Pag273) (actual value AQ) 
●  On-delay  (Page 160) (current time Ta) 
●  Off-delay (Page 164) (current time Ta)