Siemens 6ED1050-1AA00-0BE8 User Manual

Page of 372
 
Technical data 
 
A.13 Technical data: LOGO! AM2 AQ 
LOGO! 
Manual, 04/2011, A5E03556174-01 
341
 
 
LOGO! AM2 RTD 
Cable length (shielded) 
max. 10 m 
Interference frequency  
suppression 
55 Hz 
A.13 
Technical data: LOGO! AM2 AQ 
 
 
LOGO! AM2 AQ 
Power supply 
Input voltage 
24 V DC 
Permissible range 
20.4 ... 28.8 V DC 
Power consumption 
35 ...90 mA 
Voltage failure buffering 
typ. 5 ms 
Power loss at 24 V 
0.9 ... 2.2 W 
Electrical isolation 
No 
Reverse polarity protection 
Yes 
Ground terminal  
for connecting ground and shielding of the analog 
output line. 
Analog outputs 
Number 
Voltage range 
0 ... 10 V DC 
Voltage load 
≥5 kΩ 
Current output 
0/4...20mA 
Curreny load 
≤250 Ω 
Resolution 
10 bit, normalized to 0 ... 1000 
Cycle time for analog output 
depending on installation (50 ms) 
Electrical isolation 
No 
Line length (shielded and twisted) 
max. 10 m 
Error limit 
Voltage output: ± 2.5 % FS 
Short circuit protection 
Voltage output: Yes (affect neighboring voltage output) 
Overload protection 
Voltage output: Yes (affect neighboring voltage output) 
 
 
 
Note 
The 0/4 ... 20 mA current output is only possible when the module is used with a LOGO! 
0BA6 or LOGO! 0BA7 Base Module.