Siemens 6ED1050-1AA00-0BE8 User Manual

Page of 372
 
LOGO! installation and wiring 
 
2.3 Wiring LOGO! 
LOGO! 
Manual, 04/2011, A5E03556174-01 
49
 
2.3.3 
Connecting LOGO! inputs 
Requirements 
At the inputs you connect sensor elements such as: momentary pushbuttons, switches, light 
barriers, daylight control switches etc.  
Sensor characteristics for LOGO! 
 
LOGO! 12/24RCE 
LOGO! 12/24RC 
LOGO! 12/24RCo 
LOGO! 24/24o 
LOGO! 24C/24Co 
LOGO! DM8 
12/24R 
LOGO! DM8 
24 
 
I3 ... I6 
I1,I2,I7,I8 
I3 ... I6 
I1,I2,I7,I8 
I1 ... I8 
I1 ... I8 
Signal status 0 
Input current 
< 5 V DC 
< 0.85 mA 
< 5 V DC 
< 0.05 mA 
< 5 V DC 
< 0.85 mA 
< 5 V DC 
< 0.05 mA 
< 5 V DC 
< 0.85 mA 
< 5 V DC 
< 0.85 mA 
Signal status 1 
Input current 
> 8.5 V DC 
> 1.5 mA 
> 8.5 V DC 
> 0.1 mA 
> 12 V DC 
> 2 mA 
> 12 V DC 
> 0.15 mA 
> 8.5 V DC 
> 1.5 mA 
> 12 V DC 
> 2 mA 
 
 
LOGO! 24RC (AC) 
LOGO! 24RCo (AC) 
LOGO! DM8 24R (AC) 
LOGO! 24RC (DC) 
LOGO! 24RCo (DC) 
LOGO! DM8 24R (DC) 
LOGO! 230RCE (AC) 
LOGO! 230RC (AC) 
LOGO! 230RCo (AC) 
LOGO! DM8 230R (AC) 
LOGO!230RCE (DC) 
LOGO! 230RC (DC) 
LOGO! 230RCo (DC) 
LOGO! DM8 230R (DC) 
Signal status 0 
Input current 
< 5 V AC 
< 1.0 mA 
< 5 V DC 
< 1.0 mA 
< 40 V AC  
< 0.03 mA 
< 30 V DC  
< 0.03 mA 
Signal status 1 
Input current 
> 12 V AC 
> 2.5 mA 
> 12 V DC 
> 2.5 mA 
> 79 V AC 
> 0.08 mA 
> 79 V DC 
> 0.08 mA 
 
 
LOGO! DM16 24R 
LOGO! DM16 24 
LOGO! DM16 230R (AC)  LOGO! DM16 230R (DC) 
Signal status 0 
Input current 
< 5 V DC 
< 1.0 mA 
< 5 V DC 
< 1.0 mA 
< 40 V AC  
< 0.05 mA 
< 30 V DC  
< 0.05 mA 
Signal status 1 
Input current 
> 12 V DC 
> 2.0 mA 
> 12 V DC 
> 2.0 mA 
> 79 V AC 
> 0.08 mA 
> 79 V DC 
> 0.08 mA 
 
 
 
Note 
The digital inputs of LOGO! 230RCE/230RC/230RCo and of expansion module DM16 230R 
are divided into two groups, each consisting of four inputs. Within the same group, all inputs 
must be operated on the same phase. Different phases are only possible between the 
groups. 
Example: I1 to I4 on phase L1, I5 to I8 on phase L2. 
The inputs of the LOGO! DM8 230R must not be connected to different phases.