LOGO! installation and wiring 
 
2.3 Wiring LOGO! 
 
LOGO! 
58
 
Manual, 04/2011, A5E03556174-01 
2.3.5 
Connecting the EIB bus 
The connection is carried out via the two-pole screw terminal (+ and -). 
5816723
%86
(,%
3URJൻ
 
Only the red-black core pair is used, the white-yellow core pair is not connected. 
Press the button "Prog ↓" to switch the CM EIB/KNX to programming mode. 
 
 
 
Note 
The button "Prog ↓ " should not be pressed too firmly. 
If the bus connection is OK, the LED lights up green. 
In programming mode, the LED lights up orange. 
 
Networking on the EIB bus 
The CM EIB/KNX takes over the communication between LOGO! and 
EIB 
and makes 
communication available via 
EIB 
inputs/outputs. 
The application of the CM EIB/KNX fills the complete LOGO! process image; that is, inputs 
or outputs which are not occupied on LOGO! can be occupied on the EIB. 
 
 
 
Note 
For detailed information about the networking of LOGO! on the 
EIB
 bus please refer to the 
LOGO! CM EIB/KNX documentation, in particular the Micro Automation Set 8.