Siemens 6ED1050-1AA00-0BE8 User Manual
LOGO! installation and wiring
2.3 Wiring LOGO!
LOGO!
62
Manual, 04/2011, A5E03556174-01
2.3.8
Connecting the Ethernet interface (0BA7 only)
LOGO! ...E
The LOGO! ...E version is equipped with a 10/100 Mbit/s Ethernet RJ45 interface.
Requirements for the network cable
You can connect a standard Ethernet cable to the Ethernet interface. To minimize
electromagnetic interference, however, Siemens recommends you use a standard Category
5 shielded twisted-pair Ethernet cable with a shielded RJ45 connector on each end.
Connecting
You connect the PE terminal to earth ground, and connect a network cable to the Ethernet
interface.
①
②
③
Earth ground
Ethernet cable, for connecting to the Ethernet interface
Ethernet status LEDs
Ethernet cable, for connecting to the Ethernet interface
Ethernet status LEDs
Ethernet status LEDs
LED
Color
Description
Rx/Tx
Flashing orange
LOGO! is receiving/sending data across Ethernet
LINK
Steady green
LOGO! is already connected to Ethernet