Siemens DataNET Hub (DNH) User Manual

Page of 97
46  
••••  Installation 
2000585-001 
Ethernet Connections, 
Continued
 
 
1.  The 10BASET data cable requires a minimum of two twisted pairs 
(transmit pair and a receive pair). The type wire used should conform 
to the AT&T D-inside wire (DWI & PDS), or IBM Type 3, or Category 
3 or 5 data grade or equivalent specifications. 
2.  The maximum length of a 10BASET data cable can not exceed 328 
feet (100 meters). Typically to increase the distance each DNH will 
connect to a hub or other type of repeater/medium converter. 
3.  The cable should be terminated at both ends with RJ-45 STP male 
connectors. The table below shows the RJ-45 wiring connections for 
the DNH end of the cable.  
Pin No. 
MDI Function 
1 TX+ 
2 TX- 
3 RX+ 
4 NC 
5 NC 
6 RX- 
7 NC 
8 NC 
 
10BASE-T Cable 
Requirements