Installation and Commissioning 
 
Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches 
78 
C79000-G8976-C186-03 
Removing the Twisted Pair Extender from the S7-300 Rail 
You require the following tools: 
●  slotted screwdriver with a 2.8 mm wide blade 
●  slotted screwdriver with a 5.5 mm wide blade 
When removing a twisted pair extender from an S7-300 rail, the basic device re-
mains in position. Follow the steps below: 
1.  To remove an extender module, remove the two covers on the extender. 
2.  Using a slotted screwdriver with a 5.5 mm wide blade, open the captive screw 
between slots 12 and 13 in the lower part of the extender module. 
3.  Remove the cover from slot 11 of the basic device. 
4.  Use a slotted screwdriver with a 2.8 mm wide blade to loosen the two captive 
slug screws on slot 11 of the basic device in the upper and lower recesses as 
far as they will go. 
5.  Push the extender module slowly to the right while keeping it straight until the 
two guide bolts of the extender module are completely outside the holes in the 
basic device. 
6.  Pull out the lower part of the extender module slightly towards the front and lift 
it from the S7-300 rail. 
7.  Replace the right side panel of the basic device so that the guide bolts fit into 
the two holes in the basic device. 
8.  Using a slotted screwdriver with a 2.8 mm wide blade, tighten the two captive 
slug screws on slot 11. The screws lock the two guide bolts, so do not use ex-
cessive force when tightening them. 
9.  Fit a suitable cover on slot 11 of the basic device. 
 
 
Note 
The basic device must not be used permanently without the right side panel.