Site Preparation
 
BlackDiamond 12800 Series Switches Hardware Installation Guide
54
For power specifications of the BlackDiamond 12800 series switches, see 
AC Power Cable Requirements
Use an AC power cable appropriate for your country. Check your local electrical codes and regulatory 
agencies for power cable requirements. The countries listed in 
 have additional requirements as 
listed in the table.
NOTE
When using dual power supplies, make sure that each AC power supply attaches to an independent power source.
Replacing the Power Cable
If the power cable plug is unsuitable and must be replaced, connect the power supply wires for the 
switch according to the following scheme:
Brown wire to the Live (Line) plug terminal, which may be marked with the letter “L” or colored 
red.
Blue wire to the Neutral plug terminal, which may be marked with the letter “N” or colored black.
Yellow/Green wire to the Ground plug terminal, which may be marked with the letter “E” (the 
Earth symbol) or colored yellow/green.
Uninterruptible Power Supply Requirements
An uninterruptible power supply (UPS) is a device that sits between a power supply (such as a wall 
outlet) and a device (such as a switch) to prevent outages, sags, surges, and bad harmonics from 
adversely affecting the performance of the device.
A UPS traditionally can perform the following functions: 
Absorb relatively small power surges. 
Smooth out noisy power sources. 
Continue to provide power to equipment during line sags. 
Table 15: AC Power Cable Requirements
Country
Requirements
USA and Canada
• The cable set must be UL-approved and CSA-certified.
• The minimum specification for the flexible cable is No. 18
AWG (1.5 mm
2
), Type SVT or SJT, 3-conductor.
• The cable set must have a rated current capacity of at least the amount rated for each 
specific product.
• The attachment plug must be either an Earth-grounding type with a NEMA 5-15P (10 
A, 110 V) configuration or a NEMA L6-15P (10 A, 208/240 V)
Denmark
The supply plug must comply with section 107-2-D1, standard DK2-1a or DK2-5a.
Switzerland 
The supply plug must comply with SEV/ASE 1011.
Argentina
The supply plug must comply with Argentinian standards.