Server Technology CW-8H Leaflet

Page of 2
Model
Available Input
 Voltages
Outlets
Available Input
 Cord
Amperage
Dimensions*
(L x W x D)
Sentry : Solutions for the Data Center Equipment Cabinet
Key Features
Sentry : CDU Technical Specifications
Sentry Switched CDU
CW-8H
High-Density Power Distribution
The Switched CDU’s combine remote configuration and management with power 
distribution and power and environmental monitoring. Reboot a single or 
dual-power server with one command. Receive SNMP-based alerts and email alerts 
when power or environmental conditions exceed thresholds. Assign users specific 
access rights to designated outlets or groups. 
Only the Switched CDU products provide the flexibility needed for all data centers 
and remote sites, including power requirements for high-amp, high voltage; UL 
60950-1 branch circuit protection; SSL & SSH security; and SNMP-based input current 
monitoring.
> Remote Power Management: 
Power cycle individual power 
outlets, or groups of power 
outlets, to remotely reboot 
servers and network devices, 
anywhere in the world.  Or, 
power-off unused power 
receptacles
> High Power Distribution: 120V, 
208V, or 230V power; 20 or 
30-Amp power input feed 
options 
> High Density:  Single power 
input feed; 8 outlets per 1U 
enclosure
> IP Access & Security:  Web 
interface, SSL, SSH, Telnet, SNMP, 
FTP, SNTP, Syslog, LDAP, LDAPS, 
TACACS
 
and RS-232 access
> Add an Expansion Module:  
Daisy chain the Switched CDU 
Expansion Module (CW/CX) for 
power management of separate 
power circuits from a single IP 
address  
> Environmental Monitoring:  
Each Switched CDU supports two 
temperature & humidity probes 
and reports conditions thru the 
Web interface
> SNMP Traps: Provide automated 
alerts for power and 
environmental conditions
> Input Current Monitor: 
Precisely measure the aggregate 
current draw (in amps) on each 
power circuit.  On-site 
verification of the input current 
with the LED digital display.  
Remote verification via browser 
or serial screen.
Power-up Sequencing: Prevent 
an in-rush power overload
 
Branch Circuit Protection
The Sentry CDU Family meets the new UL 60950-1 
requirement for branch circuit protection.  
Attention! 
The Sentry CDU products meet the above criteria by 
providing overcurrent protection with UL-listed Bussman SC fuses for  
each branch circuit. The CW-8H contains fuses within the enclosure. 
Input Current Monitoring 
The CDU’s exclusive True RMS current monitoring is critical 
to preventing overloads in high-density computing  
environments.  LED digital displays on the CDU enclosure 
report the input current of each phase or branch circuit.
              
Temperature and Humidity    
 
 
The Switched CDU supports two external probes. Each of 
these probes measure both temperature and humidity.  
Receive SNMP-based alert notifications when conditions 
exceed defined thresholds.
              
Additional Benefits:
CW-8H1-C20
CW-8H2-C20
CW-8H1-L530
CW-8H2-L630
100-120V
50/60Hz
100-120V
50/60Hz
208-240V
50/60Hz
208-240V
50/60Hz
30A
20A
30A
20A
IEC 60320/C20
Power Inlet
NEMA L5-30P
Cordset
IEC 60320/C20
Power Inlet
NEMA L6-30P
Cordset
(8) NEMA 5-20R
(8) IEC 60320/C13
(8) NEMA 5-20R
(8) IEC 60320/C13
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
17.0” x 1.75” x 7.0”
Additional Features and Specifications
Branch Circuit Protection
> Compliant to UL 60950-1
Agency Approvals
> US & Canada (cTUVus mark) to UL 60950-1:2003 and               
   CAN/CSA 22.2 No. 60950-1-03 
        
> European Union (TUVGS mark) to EN 60950-1:2001  
> FCC Class A, Part 15 
    
> CE
> EMC - EN 55022 Class A, EN 55024
Communications and Security
> 10/100 BaseT Ethernet 
        
> HTTP/HTTPS  
        
> SSLv3/TLSv1  
       
> SNMPv2   
 
        
> SSHv2
> Telnet
> LDAPv3
> LDAPS
> TACACS+
> RS-232 (Serial)
Accessories
> Optional Temperature & Humidity Probe
 
EMTH-1-1 Temperature & Humidity Probe, 10’
 
Power Cord Options
> PTCORD-1       IEC 60320/C19 - NEMA L6-20P , 10’
> PTCORD-2       IEC 60320/C19 - Schuko 10’ 
> PTCORD-3       IEC 60320/C19 - IEC 60309 (BS4343, CEE17) 
                            16/20A Blue (UK Commando) 10’
> PTCORD-4       IEC 60320/C19 - BS1363 13A (UK) 10’
> PTCORD-5       IEC 60320/C19 - 5-15P (15A Straight-Blade) 10’
> PTCORD-6       IEC 60320/C19 - 5-20P (20A Straight-Blade) 10’
> PTCORD-7       IEC 60320/C19 - L5-20P (20A Twist-Lock) 10’
> PT-ADP-C19    Cable mount IEC 60320/C19 Connector
**Enterprise View sold separtely
Expansion Module 
Model Numbers
> CX-8H1-C20
> CX-8H1-L530
> CX-8H2-C20
> CX-8H2-L630
> CX-8HE-C20
 CW-8HE-C20*
230V
50/60Hz
16A
IEC 60320/C20
Power Inlet
(8) IEC 60320/C13
17.0” x 1.75” x 7.0”
*European Model
© Server Technology, Inc. 7/2007 version. Information in this document is subject to change without notice. Sentry is a trademark of Server Technology, Inc. Patent # 7,043,543. Patent Pending. Printed in US.