4.1
Bypass/Transfer Control Switch
The SmartSwitch is furnished with a Bypass/Transfer Control switch. The switch is located 
behind the hinged, keylocked cover. Figure 6 shows the switch positions. 
Normal Mode. The switch should be left in the “Normal” position for automatic transfer control. 
Automatic transfer control is inhibited in all switch positions other than the “Normal” position. In 
the “Normal” position, the switch will connect the load to the preferred source as long as the pre-
ferred source is available. If the preferred source falls outside of the designated limits while the 
switch is in the “Normal” position and the alternate source is available and synchronized, the 
SmartSwitch will automatically transfer the load to the alternate source. To disable automatic 
transfers, place the Bypass/Transfer Control switch in any position other than “Normal.”
Man. Xfer S1. Placing the Bypass/Transfer Control switch in the “Man. Xfer S1” position com-
mands the SmartSwitch to transfer the load to source 1. If the load is already connected to source 
1, automatic transfers to source 2 will be disabled. If the load is connected to source 2, placing the 
switch in this position requests the SmartSwitch to transfer the load to source 1. The Smart-
Switch will transfer the load to source 1 if source 1 is available and synchronized to source 2. The 
SmartSwitch will automatically delay transfer to source 1 until source 1 is available and within 
the preset phase synchronization window.
Man. Xfer S2. Placing the Bypass/Transfer Control switch in the “Man. Xfer S2” position com-
mands the SmartSwitch to transfer the load to source 2.
If the load is already connected to source 2, automatic transfers to source 1 will be disabled. If the 
load is connected to source 1, placing the switch in this position requests the SmartSwitch to 
transfer the load to source 2. The SmartSwitch will transfer the load to source 2 if source 2 is 
available and synchronized to source 1. The SmartSwitch will automatically delay transfer to 
source 2 until source 2 is available and within the preset phase synchronization window.
Bypass to S1. Placing the Bypass/Transfer Control switch in the “Bypass to S1” position 
bypasses the electronics and switching module and connects the load to source 1 by way of the 
bypass switch. In this position, control power is still available in the electronics module to allow 
the bypass status indicator to remain active. All other indicators, such as source available indica-
tors, are not active in the bypass position. To avoid loss of power to the load, do not rotate 
the switch to the “Bypass to S1” position unless the load is connected to source 1 (and 
source 1 is available) when the switch is in the “Man. Xfer to S1” position.
Bypass to S2.
 Placing the Bypass/Transfer Control switch in the “Bypass to S2” position 
bypasses the electronics and switching module and connects the load to source 2 by way of the 
bypass switch. In this position, control power is still available in the electronics module to allow 
the bypass status indicator to remain active. All other indicators, such as source available indica-
tors, are not active in the bypass position. To avoid loss of power to the load, do not rotate 
the switch to the “Bypass to S2” position unless the load is connected to source 2 (and 
source 2 is available) when the switch is in the “Man. Xfer to S2” position.
Figure 6
Bypass / Transfer Control Switch