Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page of 152
STS2 Touch Screen Display
99
SiteScan Configuration
An optional RS-422 port, contained in the Comms Board, can be installed in the static transfer switch 
to provide communications with Liebert’s SiteScan. SiteScan is Liebert’s system monitoring software 
that allows you to utilize a PC to monitor the static transfer switch’s status and check alarms. See 
6.5 - Comms Board for more information on this board. 
If the STS2 will be connected to SiteScan:
• Select YES for the SiteScan choice in the Comm Options dialog box to activate the card.
Saving Your Communications Configurations
To save you communications configuration settings:
1. When you have completed the Comm Options configurations, ensure you have selected YES for all 
the settings that you want activated.
2. Select SAVE to keep the settings.
Whenever you make modifications to the any of the Comm Options, select SAVE to keep the changes.
System Options
Most System Options are configured at the factory. However, you may need to set two of the choices 
after the unit is installed: Wye Output Transformer and Remote Source Selection.
• Select SYSTEM OPTIONS from the System Settings Menu.
The System Options dialog box is displayed. 
• An option is enabled by selecting YES.
• An option is disabled by selecting NO.
Figure 60 System options
Dual Output Breaker
This selection is set at the factory. The choice is set to YES to enable both output breakers (CB3 and 
CB3A) when two are installed in the unit. If only one output breaker (CB3) is installed, the setting is 
set to NO.
PDU
This selection is set at the factory. This setting allows the LCD to draw the Mimic accordingly and 
display PDU specific metering and alarm information.