Specifications
115
15.2.11RS-232 Interface Parameters
The service terminal interface parameters are the following settings and cannot be changed.
15.2.12Maintenance Bypass
The STS2 is configured to allow the unit’s electronics to be bypassed to either input source for mainte-
nance without interruption of power to the load. 
The STS2 is furnished with key-interlocked maintenance bypass breakers to configure the bypass.
STS2 units have all electronics isolated from the input, output, and bypass connections to allow safe 
servicing of any components without access to hazardous voltages when the unit is in maintenance 
bypass.
See 10.4 - Maintenance Bypass on page 67 for instructions using the Color LCD Graphical Display 
15.2.13Fuseless Design
All STS2 units are fuseless and are UL rated for use with upstream circuit breakers only. 
15.2.14Options
The following options are available for the STS2:
Table 24
RS-232 Settings
Parameter Setting
Interface 
RS-232 Using EIA Voltage Levels
Baud Rate 
9600
Parity None
Number of Data Bits 
8
Number of Stop Bits 
1
Hardware Flow Control 
Off
Terminator <CR> 
<LF>
Handshaking Not 
supported
Structure Full 
duplex
Local Echo 
Off
Optimized Transfer
LED Display
Redundant Output Breaker
Network Interface Card (NIC)
Distribution Cabinet With I-Line Panelboard
Seismic Floor Stand - 18", 24", 30" and 36"
Input Junction Boxes and Cable
Export Crating
Comms Board w/SiteScan and Modem Interface
Internal Modem
Input Contact Isolator Board
Remote Source Selection
Programmable Relay Board
Key Lockout Switch