Installation Drawings
32
Figure 20 Circuit breaker schedule
CIRCUIT BREAKER SCHEDULE
100AMP TO 1000AMP 
STATIC TRANSFER SWITCH 2
NOTES:
1. THE STS2 AUTOMATIC MOLDED CASE BREAKERS ARE 3 POLE, 600VAC RATED WITH MAGNETIC TRIP ONLY.
2. UPSTREAM DEVICES (BY OTHERS) MUST BE USED TO PROVIDE OVERCURRENT PROTECTION. UPSTREAM     OVERCURRENT PROTECTION SHOULD HAVE AMPACITY EQUAL TO OR LESS THAN THE AMPERE     RATING OF THE STATIC SWITCH MOLDED CASE BREAKER. 
VOLTAGE
STATIC TRANSFER SWITCH 2, MOLDED CASE BREAKER SCHEDUL
E
1000A
400A
100A
250A
600A
800A
STS2
RATING
AMPACITY
VENDOR
TY
P
E
NSF
150A
SQD
WITHSTAND CURRENT
SQD
MERLIN GERIN
100K 65K 25K
NSF
NSJ
NSJ
PJ
PJ
250A
400A
600A
800A
1200A
100K 65K 25K
100K 100K 25K
100K 100K 25K
100K 65K 25K
100K 65K 25K
MERLIN GERIN
MERLIN GERIN
MERLIN GERIN
200-240V 380-480V
600V
200-240V 380-480V
600V
200-240V 380-480V
600V
200-240V 380-480V
600V
200-240V 380-480V
600V
200-240V 380-480V
600V