Liebert POWER PROTECTION STATIC TRANSFER SWITCH User Manual

Page of 152
STS2 Touch Screen Display
91
To configure the set points for each source:
1. Select SOURCE 1/2 SET POINTS from the User Settings dialog box.
The Source 1/2 Set Points dialog is displayed.
Figure 55 Source setpoints
2. Select 1 to configure the settings for Source 1.
3. Configure the settings using the keypad or dialog box that is displayed when you touch a button.
4. Select 2 for Source 2.
5. Configure the settings, as described in ste3.
6. Select SAVE to keep the settings for both sources.
The Set Points dialog is closed and the User Settings dialog is displayed.
7. Select MANUAL MAX XFER PHASE ANGLE.
A keypad is displayed.
This setting configures the maximum allowed phase difference between the sources and applies to 
all manual transfers as well as any auto retransfer. 
a. Configure this setting with a range of +/- 1-30 degrees.
The default setting is +/-15 degrees and the resolution is 1 deg.
b. Select OK to save the setting.
The setting is now displayed in the adjacent field in the User Settings dialog box.
Table 14
Set Point Parameters
Button
Range
Default
Comments
Fast UV Setting (%)
-10 to -30% of Nominal 
voltage rating
-20%
Set in increments of 1%.
Slow UV Setting (%)
-5 to -20%
-10%
Set in increments of 1%.
Slow UV detection delay
1-60 cycles
5 cycles
Units: Line Cycle
OV Setting (%)
+5% to +20%
+10%
Set in increments of 1%.
OV Detection Delay
1-255 cycles
3 cycles
Units: 1/4 Line Cycle
I-PK Xfer Lockout
0 – 3.0 multiplied by 
the unit current rating.
2.5 * Unit 
Current Rating
I-peak xfer lockout detection point. 
Units: Amps RMS. Select the HI or 
LO buttons to configure your setting.