Configuration: How to Configure the System
Symmetra MW with External Bypass Static Switch Operation Manual - 990-1377D-001
15
Change the touch-screen settings:
– Brightness: Place the finger on the indicator 
and slide it left or right to the desired setting.
– Contrast: Place the finger on the indicator and 
slide it left or right to the desired setting.
– Backlight mode: Select “Always on” or “Off 
after inactivity”.
– Backlight timeout (minutes): Select the time 
limit for turning off the screen backlight.
– Recalibrate Display: Press this button to 
initiate the calibration of the screen.
Note: If the backlight mode is set to “Always on” this will reduce the lifetime of the display.
Note: If a display reboot is required, it can be achieved by recalibrating the display.
How to configure the Modbus Settings screen
The Modbus Settings screen allows monitoring of the UPS by a Building Management System (BMS).
Press the Modbus Settings button on the User 
Configuration screen to access the Modbus 
Settings screen.
Change the modbus settings:
– BMS modbus RTU address: The modbus 
address of the UPS device.
– Baud rate: Select 9600, 19200, 38400, 57600, 
or 115200.
– Parity: Select None, Odd, or Even.
Press Apply Changes to complete the changes.