Fujitsu C122-E119EN User Manual

Page of 109
1.3
 Installation Specifications
This section lists the installation specifications of each device.
 
-
-
-
 
1.3.1
 PRIMEQUEST 1800E2 installation specifications
TABLE 1.2 PRIMEQUEST 1800E2 installation specifications
Item
Description
External
dimensions
[mm (in.)]
Width
482 (18.98)
Depth (*1)
800 (31.50)
Height
530 (20.87)
Weight [kg (lb)] (*2)
150 (330)
Air conditioning
requirements
Maximum heat output [kJ/h (BTU/h)]
14,400 (13,649)
Exhaust air
flow [m
3
/min
(ft
3
/min)] (*3)
FAN at low speed (Low)
14 (494)
FAN at normal speed (Normal)
21 (742)
FAN at high speed (High)
24 (848)
Temperature
and humidity
requirements
(*4)
Operating
Temperature [°C (°F)]
(*5)
Humidity [%RH]
20 to 80
Maximum wet-bulb
temperature [°C (°F)]
29 (84.2)
Non-operating (*6) Temperature [°C (°F)]
0 to 50 (32 to 122)
Humidity [%RH]
8 to 80
Maximum wet-bulb
temperature [°C (°F)]
29 (84.2)
Noise [dB] (*7) (*8)
61
Acoustic power level [B] (*8)
7.8
Allowable
vibration [m/
s
2
 (gal)]
Operating (including standby state)
4.0 (400) (synthetic seismic
waves)
Non-operating (*9)
10.0 (1000) (synthetic
seismic waves)
Allowable dust concentration [mg/m
3
]
0.15
Power
requirements
Input voltage and number of phases
200 to 240 VAC ±10%
Frequency and fluctuation range
50/60 Hz +2/-4%
PRIMEQUEST 1000 Series Hardware Installation Manual
CHAPTER 1 Installation Information
6
C122-H004-07EN