2.6
 Shutoff Characteristic of the Customer's Distribution Panel
(Only When Connected to the Power Distribution Box)
To protect the device when it is connected to the customer's distribution panel through a power distribution box,
the breaker of the device (or the power distribution box) must trip before the corresponding breaker in the customer's
distribution panel. For this reason, the breakers in the customer's distribution panel must meet the characteristics
listed in 
characteristics.
 
TABLE 2.8 Breaker characteristics for the customer's distribution panel
Power input
Device name
Breaker for use in countries other than
European countries (*)
Breaker for use in
Europe (*)
200 to 240 VAC
Power distribution box 30 A
32 A
* Capacity of a breaker in the customer's distribution panel
 
Use a long-time-delay type of breaker whose characteristics correspond to phase D shown in 
 
PRIMEQUEST 1000 Series Hardware Installation Manual
CHAPTER 2 Connection Information
41