A.2.2
 Requirements for mounting in a rack manufactured by another company
When mounting the PRIMEQUEST products in a rack manufactured by another company, customers need to
confirm on their own responsibility that the rack meets the PRIMEQUEST product specifications and requirements.
 
Note
Fujitsu does not guarantee there will be no problems arising from the mounting of the PRIMEQUEST 1000 series
server (including peripheral devices) in a rack manufactured by another company.
Examples: Cooling problem due to an insufficient supply of cooling air because of the rack structure, and insufficient
earthquake-resistance because the rack manufactured by another company is not strong enough
If mounting in a rack manufactured by another company cannot be avoided, confirm that the rack satisfies all of
the following structural requirements.
 
Conditions of rack depth