Telephony Gateway 
Mount to Rack or Wall 
The SpectraLink 8000 Telephony Gateways can be wall mounted 
either horizontally or vertically. Gateways may also be rack mounted 
in a standard 19-inch rack. A Rack Mount Kit must be purchased 
separately for a rack mount installation. 
To Mount 
Gateways… 
Connector A is… 
Mount the Units… 
Clearance Between Gateways 
Horizontally 
To the right side of 
the SpectraLink 
8000 Telephony 
Gateway, with 
labels in correct 
position. 
On top of one 
another 
Leave a little more than 1/4” between 
adjacent units, allowing easy removal of 
units via the keyhole openings on the rear 
panel. 
Do not leave more than 1/2” spacing or the 
ESD bonding strap will not fit correctly. 
To set the desired unit spacing, leave (0.9” 
+ desired gap) between adjacent mounting 
holes. 
Vertically 
At the top of the 
SpectraLink 8000 
Telephony 
Gateway 
Side by side 
Adjacent units should be physically 
touching. 
 
PN: 1725-36028-001_T.doc 
 