Panasonic FP User Manual

Page of 194
FP Web-Server V2.11 
 
7.1 Details on the FP Web-Server's Web Page Functions 
89 
The individual HTML commands can be entered (exactly as described above) into the HTML 
code of the page and then adjusted respectively. Some HTML editors provide additional help 
and automatic generation for creating submit fields. The commands have the following 
significance: 
ACTION="
/plcpost
"
 
Enter precisely like this. CGI function of the FP 
Web-Server. 
METHOD="
POST
"
 
Enter precisely like this. Method of the CGI call. 
TARGET="
SUBWIN
"
 
Enter precisely like this. Display the result in a separate 
window. 
ONSUBMIT="
opensubwin(200,100)
"
 
Enter precisely like this. Java Script call and window 
size. 
Enter DT204 
Variable text will be displayed as seen. 
NAME="
DT204_5_u
"
 
Specification of the memory address in the PLC and 
interpretation of the input format. 
SIZE="
6
"
 
Width of the input window in number of characters. 
VALUE="
{DT204_5_u}
"
 
Initial value of the input field. Pre-allocation of the Edit 
field. 
Only for the definition of buttons in case A): 
TYPE="
submit
"
 
Enter precisely like this. Function of the [SUBMIT] 
buttons. 
NAME="
Button
"
 
Enter precisely like this. Name of the [SUBMIT] button. 
VALUE="
 
set 
"
 
Variable labeling of the [SUBMIT] buttons. 
 
 
7.1.12.1 Examples on PLC Data Entries via HTML Page 
a) Decimal 
numbers 
Entry format 
User entry 
Data in PLC register 
DT201_16_u 
12 
DT201= 12 (0C hex) 
DT201_16_d -32768 
DT201= 
-32768 
(8000hex) 
DT202_16_ld 1234567 
DDT202=1234567 
(12D687hex) 
DT202_16_f 
123.4 
DDT202=123.4 (42F6CCCD hex) 
DT202_16_f 
1.2e4 
DDT202=12000 (463B8000 hex) 
b) Strings 
Entry format 
User entry 
Data in PLC register 
DT602_16_S 1234 
DT602-DT603="1234" 
DT602_16_S 
123 
DT602-DT603="123?"   (? is unchanged) 
DT600_16_s 
1234 
DT601=4 DT602-DT603="1234" (DT600 > 3) 
DT602_16_c 
ABC 
DT602="A?"   (? is unchanged) 
c) Hex 
entries: 
In the latest version also the format type characters 'x' and 'X' are allowed for 
hexadecimal PLC data entries. Hex data entries are possible for 16-bit 
(name="DT200_6_X") and 32-bit (name="DT300_16_lx") PLC data registers: 
Entry format 
User entry 
Data in PLC register 
DT201_16_X 
7b 
DT201=  123 (007B hex)