12.2  Modbus-TCP Server of the FP Web-Server in General 
The FP Web-Server can be accessed by a Modbus-TCP client (SCADA) via Ethernet for PLC 
data communication. To do so, the FP Web-Server requests PLC data (MEWTOCOL protocol) 
via the 3-pin or/and 9-pin RS232C port. The 9-pin RS232C can alternatively communicate via 
Modbus-RTU protocol with a Modbus-RTU slave unit. 
 
Modbus-TCP communication can also occur via modem. To do so, the client must first dial up 
the FP Web-Server's PPP-Server to establish a modem connection. 
The Modbus-TCP server can handle up to 6 client connections simultaneously. If there are 
already 6 connections and another client wishes to establish a connection, the oldest 
connection can be ended automatically.  
Up to 3 different port numbers are possible. Alternatively, these ports can be switched to UDP 
communication where each UDP port is assigned one task. Both of the FP Web-Server's 
RS232C ports can be addressed. 
 
Features: 
•  The Modbus-TCP client can address the FP Web-Server's two RS232C ports 
(MEWTOCOL or Modbus-RTU) by using a port number or unit ID. 
Detailed information: 
For more information on Modbus-TCP server settings and the respective server 
functions, please refer to the online help under the keyword "Modbus-TCP Server 
Settings".