13.1 IEC 60870 General Functions 
153 
Perform the following steps to disable extended MEWTOCOL commands for FPWIN Pro: 
 
1.  Locate file "NAiS_MewPLC.DAT" under C:\Program Files\NAiS MEWNET 
2.  Open "NAiS_MewPLC.DAT" with a text editor, e.g. Notepad 
3.  Find the section for your PLC, e.g. [FPSIGMA] or [FP2] 
4.  Set the parameter EXTCMD=0 to zero 
5.  Save changed file "NAiS_MewPLC.DAT" 
6.  Restart FPWIN Pro 
 
13.1.1  Details of the IEC 60870 Configuration: Modem and Multipoint Settings 
1.) Multipoint with FP Modem-EU 
•   line parameter:  half duplex 1200 bps (independent from the RS232C baud rate) 
- communication via V.23 mode 2 norm via twisted pair cables 
- terminator: see manual of FP Modem-EU 
•   modem setup: initialization with PC and terminal program 
- set all DIP switches of the modem to OFF and connect to the PC 
- set the terminal to 1200 bps, 8 data byte, parity ODD and 1 stop bit (see note 1) 
- Use the terminal to reset the modem to AT&F&W 
- store the settings of RC232 format (see note 1) 
- AT*W=1200,8,O,1 
- set modem DIP switch 2 to ON 
•  connect the modem to RTI (RTU) via the standard modem cable 1:1 
•  RS232C signal (PC mode): DCD shows status line, i.e. line is busy 
•  RTS initializes sending: CTS after RTS means OK to send 
• Settings 
for 
RTI (Lian98 from Ver 1.0.1.2 onwards): 
- baud rate, data byte, parity, stop bits set to same values as the modem (* Note) 
- timeout 280ms minimum 
- modem: half duplex 
- transmission: unbalanced 
• Settings 
of 
RTU (IEC Communicator): 
- baud rate, data byte, parity, stop bits set to same values as the modem (* Note) 
- handshake: RTS/CTS