Siemens TPS3 User Manual

Page of 16
UL 1283 required language concerning the installation of EMI Filters
a)  An  insulated  grounding  conductor  that  is  identical  in  size  and
insulation material and thickness to the grounded and ungrounded
circuit supply conductors, except that it is green with or without one
or more yellow stripes, is to be installed as part of the circuit that
supplies the filter. Reference should be made to Table 250-122 of
the  National  Electrical  Code  regarding  the  appropriate  size  of  the
grounding conductor.
b) The grounding conductor mentioned in item a is to be grounded
to earth at the service equipment or other acceptable building earth
ground such as the building frame in the case of a high-rise steel-
frame structure.
c) Any attachment-plug receptacles in the vicinity of the filter are
to be of a grounding type, and the grounding conductors serving
these receptacles are to be connected to earth ground at the service
equipment  or  other  acceptable  building  earth  ground  such  as  the
building frame in the case of a high-rise steel-frame structure.
d) Pressure terminal or pressure splicing connectors and soldering
lugs used in the installation of the filter shall be identified as being
suitable for the material of the conductors. Conductors of dissimilar
metals  shall  not  be  intermixed  in  a  terminal  or  splicing  connector
where physical contact occurs between dissimilar conductors unless
the device is identified for the purpose and conditions of use.
Additional instructions for TPS3 01 & L1 SPDs including:

W option Suffix:
The W option includes respositioned phase connection tabs that allow 
for wire connections to a circuit breaker within the panelboard. This 
differs from non-W models, which bolts directly to bus bars.
The circuit breaker serves as a disconnector device and overcurrent 
protection to the connecting conductors. The TPS3 SPD includes 
internal overcurrent and overtemperature protective equipment. The 
breaker does not provide  overcurrent protection to the SPD.
Recommended breaker and conductor size is 60A with a 6 AWG 
conductors. Other combinations are possible. Terminal lugs will 
accept 2-14 AWG. Breaker size should be at least 20A. All applicable 
codes must be followed.
Circuit breaker MUST be located immediately adjacent to SPD to 
minimize lead lengths. Move or adjust breaker positions as appropriate. 
Every effort must be taken to reduce lead lengths. Failure to install 
short leads will degrade SPD performance.
Install appropriate circuit breaker in panelboard.
Prior to installing SPD, rotate and tighten lug terminals toward breaker 
location. 
Mount the SPD using supplied hardware.
Connect the neutral connection by wire or bracket as appropriate.
Install conductors, short and straight as possible. Use gentle radius 
on any bends. Do not kink wires. Prevent wires from encroaching 
breaker locations.
Torque all connections to the values specified on the installation and 
maintenance instruction label affixed to the rear of the dead front.
Replace dead front supports and trim.
Energize breaker and confirm proper SPD operation.
7