Siemens TPS3 User Manual

Page of 16
Introduction
Thank you for choosing Siemens TPS3 Surge Protective Device
(SPD).  This  is  a  high  quality,  high  energy  surge  suppressor
designed to protect sensitive equipment from damaging transient
overvoltages.
Proper installation is important to maximize performance. Please
follow the steps outlined herein.
This  entire  user  manual  should  be  read  prior  to  beginning
installation. These instructions are not intended to replace national
or  local  codes.  Follow  all  applicable  electrical  codes  to  ensure
compliance. Installation of this SPD should only be performed
by qualified electrical personnel.
All Siemens SPDs are extensively tested in accordance with industry
standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62,
C62.72, UL 1449, UL 1283, IEC 61643, etc.
Warning and Safety Information
This  equipment  contains  hazardous  voltages.  Death,  serious
injury, or property damage can result if safety instructions are not
followed. Only qualified personnel should work on or around this
equipment after becoming thoroughly familiar with all warnings,
safety notices, and maintenance procedures contained herein.
The  successful  and  safe  operation  of  this  equipment  is
dependent  upon  proper  handling,  installation,  operation,  and
maintenance.
Qualified Person
For the purposes of this manual and product labels, a QUALIFIED
PERSON is one who is familiar with the installation, construction,
and operation of this equipment, and the hazards involved. In
addition, he or she has the following qualifications:
(a)  Is trained and authorized to energize, deenergize, clear,
ground and tag circuits and equipment in accordance
with established safety practices.
(b)  Is trained in the proper care and use of personal protective
equipment (PPE) such as rubber gloves, hard hat, safety
glasses or face shields, flash clothing, etc. in accordance
with established safety practices.
(c)  Is trained in rendering first aid.
Danger
For  the  purposes  of  this  manual  and  product  labels,  DANGER
indicates an imminently hazardous situation, which, if not avoided,
will result in death or serious injury.
Warning
For the purposes of this manual and product labels, WARNING
indicates failure to following these instructions can result in death,
serious injury, or equipment damage.
Caution
For the purposes of this manual and product labels, CAUTION indicates
a potentially hazardous situation which, if not avoided, could result
in minor or moderate injury.
These instructions do not purport to cover all details or variations in
equipment, nor to provide for every possible contingency to be met
in connection with installation, operation or maintenance. Should
further information be desired or should particular problems arise
which are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to the local Siemens sales office.
Do Not Hi-Pot Test SPDs
Any factory or on-site testing of power distribution equipment that 
exceeds normal operating voltage such as high-potential insulation 
testing, or any other tests where the suppression components 
will be subjected to higher voltage than their rated Maximum 
Continuous Operating Voltage (MCOV) must be conducted with 
the SPD disconnected from the power source. For 4-wire systems, 
the neutral connection at the SPD must also be disconnected prior 
to performing high-potential testing and then reconnected after 
test completion. 
Failure  to  disconnect  SPD  and  associated  components  during 
elevated voltage testing will damage the SPD and will void the 
warranty.
Limited Warranty
Siemens warrants its AC Panel protection products against defective
workmanship and materials for 10 years. Liability is limited to the repair
or replacement of the defective product at Siemens’ option. A Return
Material Authorization number (RA#) must be given by the company
prior to the return of any product. Returned products must be sent
to the factory with the transportation charges prepaid. In addition,
the company also warranties unlimited replacement of modular and
component parts within the warranty period previously described.
The company specifically disclaims all other warranties, expressed or
implied. Additionally, the company is not be responsible for incidental
or consequential damages resulting from any defect in any product
or component thereof.
The  sales  contract  contains  the  entire  obligation  of  Siemens.  This
instruction  manual  shall  not  become  part  of  or  modify  any  prior
existing agreement, commitment or relationship.
Unpacking and Preliminary Inspection
Inspect  the  entire  shipping  container  for  damage  or  signs  of
mishandling before unpacking the unit. Remove the packing material
and further inspect the unit for any obvious shipping damages. If any
damage was found and is a result of shipping or handling, immediately
file a claim with the shipping company and forward a copy to your local
Siemens sales office.
1