Liebert 100 Leaflet

Page of 1
Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH  43229  
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169 
EMAIL: info@control-concepts.com • Web Site: www.Liebert.com 
82247 Rev 0 
 
 
 
Liebert AC Power Low Exposure Transient Voltage Surge Suppressor, electronic grade surge 
protective device designed with sine wave tracking to protect electronic equipment and 
microprocessor-based systems from transients on distribution panels, branch panels, or equipment in 
low exposure locations. Dry contacts for remote indication standard.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
AC Power Low Exposure TVSS Technical Specification
Connection Type ................................................. Parallel 
Operating Voltage Range................................... +/-15% 
Fault Current Rating (AIC).................................. 14 kAIC 
Dimensions ..................... .................................... 4.72”x4.72”x2.36” 
Operating Frequency Range ............................. 47 – 63 Hz 
Capacity................................................................ Continuous 
50   EMI/RFI Attenuation ................................... 40 dB 
Response Time.................................................... <0.5 ns 
Dry Contract rating.............................................. 125vac, 8.0A, 1.0pf 
Operating Temperature ...................................... -40ºc to +50ºc 
Operating Humidity............................................. 0% to 95% 
Status Indication.................................................. LED, Dry Contacts 
Certifications........................................................ UL 1449, CUL, CE, ISO 9001 
Warranty ............................................................... 5 Years 
 
UL 1449 (second edition) Classification 
 120 
volt 
systems.................................400 volts all modes 
 
208 through 277 volt systems ..........800 volts all modes 
 480 
volt 
systems.................................1,500 volts all modes 
ORDERING INFORMATION 
 
Building A Model Number: LPL  1  2  3  
 
1: Nominal Voltage Requirements 
2: System Configuration 
3: Surge Current Capacity 
 
 
Nominal Voltage Requirements 
Model ID 
System Configuration 
Model ID 
 L-N 
L-L 
L-G  
 
 120 ........N/A....... 120 
120 
 Single (2 Wire + Gnd)  
N or L
 
 120  .......208 ...... 120 
120 
 Split (3 Wire + Gnd) 
S
 
 120 ........240....... 120 
120 
 Wye (4 Wire + Gnd)  
Y
 
 N/A ........208....... 208 
208 
 Delta Hi-Leg (4 Wire + Gnd) 
H
 
 230 ........400....... 230 
230 
 Delta (3 Wire + Gnd) 
D
 
 N/A ........240....... 240 
240
 
 277 ........480....... 277 
277
 
 N/A ........400....... 400 
400
 
 N/A ........480....... 480 
480 
 
 
 
Surge Current Capacity    
Model ID 
 
 100 kA/Phase 
100 
 
 
 
 
 
(L-N: 50 kA + L-G: 50 kA; N-G: 50 kA) 
 
 
 
 
 
  50 kA/Phase  
50 
 
 
 
 
(L-N: 25 kA + L-G: 25 kA; N-G: 25 kA) 
 
 
 
 
PANEL I.D. 
MODEL NUMBER(S) 
 
 
 
 
 
 
 
 
 
 
 
 
 
  25 kA/Phase  
25 – 2   
 
 
 
(L-N: 25 kA; N-G: 25 kA) 
 
 
 
 
 
 
 
Job Name _______________________  
Model # _________________________  
Date ___________________________  
Qty ____________________________  
Quote # _________________________