Liebert 100 - 2 Leaflet

Page of 1
 
 
 
 
Liebert AC Power Medium Exposure Transient Voltage Surge Suppressor, a surge protective 
device designed with sine wave tracking to protect electronic equipment and microprocessor-based 
systems from transients on distribution panels or any medium exposure locations. 
 
 
Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH  43229  
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169 
EMAIL: info@control-concepts.com • Web Site: www.Liebert.com 
                            82246 Rev 0 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
AC Power Medium Exposure TVSS Technical Specification
Connection Type................................................Parallel 
Operating Voltage Range 
.................................+/-15% 
Fault Current Rating (AIC) ................................65 kAIC 
Dimensions......................... (160 kA units) ......8”x6”x4” 
.............................................. (100 kA units) ......6”x4”x3” 
Operating Frequency Range............................47 – 63 Hz 
Capacity ..............................................................Continuous 
50   EMI/RFI Attenuation..................................40 dB 
Response Time ..................................................<0.5 ns 
Operating Humidity ...........................................0% to 95% 
Operating Temperature.....................................-40º c to +50ºc 
Dry Contact Rating ............................................
125vac, 8.0A, 1.0pf 
Status Indication 
................................................LEDs, Dry Contacts 
Certifications ......................................................UL 1449, CUL, ISO 9001 
Warranty..............................................................5 Years Parts 
 
UL 1449 (second edition) Classification 
 120 
volt 
systems ................................ 400 volts all modes 
 
208 and 277 volt systems ................. 800 volts all modes 
 480 
volt 
systems ................................ 1,500 volts all modes 
100 kA
 
160 kA 
 
ORDERING INFORMATION 
 
Building A Model Number: LPM  1  2  3
 
 
1: Nominal Voltage Requirements 
2: System Configuration 
3: Surge Current Capacity 
 
 
 
 
Nominal Voltage Requirements 
Model ID 
System Configuration 
Model ID 
  
L-N 
L-L 
 
L-G  
 
 120........ N/A........120 ............................120 
 Single (2 Wire + Gnd)  
N or L
 
 120 ....... 208 .......120 .................... .......120 
 
 Split (3 Wire + Gnd) 
S
   
 120........ 240........240 .................... .......120 
 
 Wye (4 Wire + Gnd)  
Y
   
 N/A........ 208........208 .................... .......208 
 
 Delta Hi-Leg (4 Wire + Gnd) 
H
 
 
 230........ 400........230 .................... .......230 
 
 Delta (3 Wire + Gnd) 
D
 
 
 N/A........ 240........240 .................... .......240 
 
 
 
 277........ 480........277 .................... .......277 
 
 N/A........ 400........400 .................... .......400 
 
 
 N/A........ 480........480 .................... .......480 
 
 
 
Surge Current Capacity    
Model ID 
Surge Current Capacity    
Model ID 
 
 
 
 
 160 kA/Phase ............................................160 
 100 kA/Phase  .......................... 100 – 2 
 
(L-N: 80 kA + L-G: 80 kA; N-G: 80 kA) 
 (L-N: 100 kA; N-G: 100 kA) 
 
 
PANEL I.D. 
MODEL NUMBER(S) 
 
 
 
 
 
 
 
 
 
 
Job Name_______________________
Model# _________________________
Date ___________________________
Qty ____________________________
Quote# _________________________