Liebert 100-1000A User Manual

Page of 152
Installation Drawings
38
Figure 25 Control wiring for the input contact isolator board option
2
1
5
3 4
6 7
14
11
9
8
10
12 13
15 16
“NO CUSTOMER CONNECTION”
INPUT CONTACT ISOLATOR BOARD
02-810012-XX
J51
PS213002
Rev. 03
NOTES:
1. Customer control wiring connection points are Terminals 1 through 16
2. Customer-provided, normally open, dry contacts for user alarm messages.
3. Refer to installation, operation and maintenance manual for configuring the 
Input Contact Isolator board option.
4. All control wiring (by others) must be run separate from power wiring. Control 
wiring runs should not be combined in the same conduit.
5. Refer to static transfer switch control connection diagram (Figure 21 or 22) for 
location of Input Contact Isolator board option.
6. Signal voltage: 100mA @ 12VDC.
7. Maximum cable length 500 ft. (152 m) with #16 AWG flexible, stranded cable.
8. All wiring must be in accordance with national and local electrical codes.
9. When the Transfer Inhibit option is supplied, connect a N.O. dry contact 
(customer-supplied) to Input Contact 8 (Pins 15 and 16). When the customer 
contact closes, transfers will be inhibited as long as the contact remains closed. 
Input Contact 8 is factory-set so no setup is required. The Transfer Inhibit option 
prevents Input Contact 8 from being used for any other input.
Table J51
Input
Contact
Pin No.
1
1
2
2
3
4
3
5
6
4
7
8
5
9
10
6
11
12
7
13
14
8
15
16