Liebert 100-1000A User Manual

Page of 152
Installation Drawings
45
Figure 32 Installation drawing, seismic floor stand 100-250A
INSTALLATION DRAWING FOR
SEISMIC FLOOR STAND
100-250A STS2 
INSTALLATION NOTES:
1. CHECK ALL HARDWARE FOR PROPER TORQUE PRIOR TO INSTALLATION.
2. INSTALL REAR LOWER STS2 BRACKET TO THE FLOOR STAND USING EXISTING HOLES WITH BENT FLANGE 
    FACING THE FRONT OF THE FLOOR STAND (FIG. 3 AND FIG 4, DWG PS215001). USE M12-1.75X40mm 
CAP SCREW, 
    SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS. 
3. LOOSEN THE STS2 ADJUSTABLE LEVELER FEET NUTS (SEE DETAIL C; DWG PS215001). INSTALL REAR 
    UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH TABS FACING OUT 
    (FIG 1 AND FIG 2, PS215001). INSTALL FRONT UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE 
    OF THE STS2 WITH BENT FLANGE FACING TO THE FRONT. (FIG.1 AND FIG 2, PS215001). USE M12-1.75X40mm CAP 
    SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS. RETIGHTEN LEVELER FEET NUTS. 
4. FLOOR STAND CAN BE MOUNTED NEXT TO A WALL IF NEEDED, REAR ACCESS NOT REQUIRED. 
    INSTALL FLOOR STAND WITH FEET ORIENTATED AS SHOWN IN (BOTTOM VIEW; DWG PS215000). 
    TO ADJUST VERTICAL HEIGHT OF FLOOR STAND FEET, LOOSEN, ADJUST AND TIGHTEN THE NUTS AND 
    JAM NUT SHOWN 
IN (FOOT DETAIL A & B; ON DWG PS215000). FLOOR STAND MUST BE LEVEL AND ALL FEET 
    MUST BE TOUCHING 
THE FLOOR. ATTACH FLOOR STAND FEET USING 1/2" X 4" RED HEAD TRUBOLTS 
    EXPANSION ANCHORS 
(FEILD SUPPLIED) (2) PER FOOT.
5. ROLL THE STS2 ONTO THE FLOOR STAND SO THAT THE TABS ON THE (REAR UPPER STS2 BRACKET) 
    FIT INTO THE 
SLOTS ON THE (REAR LOWER STS2 BRACKET). TABS TO EXTEND AT LEAST 1/2" THROUGH 
    FLOOR STAND 
BRACKET (FIG. 2, DWG PS215002). 
6. INSTALL THE L
OWER FRONT BRACKETS (FIG 1, DETAIL A; DWG PS215002). ATTACH BRACKET TO STS2 USING 
    M10-1.50X30mm 
CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 31 FT-LBS. 
    ATTACH BRACKET 
TO FLOOR STAND USING M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND 
    FLAT WASHER
 AND TORQUE TO 53 FT-LBS
TOP VIEW
FRONT VIEW
BOTTOM VIEW
36.9"
29.9"
NUT
JAM NUT
NUT
FOOT DETAIL A
FOOT DETAIL B
B
ISOMETRIC VIEW 250A FLOOR STAND
SEE HEIGHT
TABLE
A
MOUNTING PLATE
ALIGN FOOT PARALLEL TO 
MOUNTING PLATE AS SHOWN
29.44"
TYP.
2.47"
TYP.
17.48"
TYP.
2.47"
TYP
.625" DIA x 2
TYP.
HEIGHT TABLE
P/N OF FLOOR 
STAND:
H
E
IG
H
T
HEIGHT MAX:
HEIGHT MIN:
523401G1
1
8
.0
"
1
9
.2
5
"
1
6
.7
5
"
523402G1
2
4
.0
"
2
5
.2
5
"
2
2
.7
5
"
523403G1
3
0
.0
"
3
1
.2
5
"
2
8
.7
5
"
523404G1
3
6
.0
"
3
7
.2
5
"
3
4
.7
5
"
6" TYP.
HARDWARE TORQUE CHART
1
.0
" N
U
T
3
20 
FT 
LBS
M8 - 1.25
16FT - LBS
M10 - 1.5
31 
FT 
LBS
M12 - 1.75
5
3
 F
T
 -
L
B
S
PS215000 REV
. NO. 0