Liebert 100-1000A User Manual

Page of 152
Installation Drawings
53
Figure 40 Installation drawing, seismic floor stand 800-1000A
A
B
TOP VIEW
FRONT VIEW
BOTTOM VIEW
ISOMETRIC VIEW 
36.9"
83.9"
SEE HEIGHT
TABLE
29.44"
TYP.
2.47"
TYP.
71.55"
TYP.
2.47"
TYP
MOUNTING
PLATE
ALIGN FOOT PARALLEL 
TO MOUNTING PLATE AS 
SHOWN
FOOT DETAIL A
FOOT DETAIL B
RIGHT SIDE VIEW
INSTALLATION NOTES:
1. CHECK ALL HARDWARE FOR PROPER TORQUE PRIOR TO INSTALLATION.
2. INSTALL REAR LOWER STS2 BRACKET TO THE FLOOR STAND USING EXISTING HOLES WITH 
    BENT FLANGE FACING THE FRONT OF THE FLOOR STAND (FIG. 3 AND FIG 4, DWG PS217001). 
    USE M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS. 
3. LOOSEN THE STS2 ADJUSTABLE LEVELER FEET NUTS (SEE DETAIL C; DWG PS217001). INSTALL REAR 
    UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH TABS FACING OUT 
    (FIG 1 AND FIG 2, PS217001). INSTALL FRONT UPPER STS2 BRACKET USING EXISTING HOLES ON 
    UNDERSIDE OF THE STS2 WITH BENT FLANGE FACING TO THE FRONT. (FIG.1 AND FIG 2, PS217001). 
    USE M12-1.75X40mm 
CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO
    53 FT-LBS. RETIGHTEN LEVELER FEET NUTS. 
4. FLOOR STAND CAN BE MOUNTED NEXT TO A WALL IF NEEDED, REAR ACCESS NOT REQUIRED. 
    INSTALL FLOOR STAND WITH FEET ORIENTATED AS SHOWN IN (BOTTOM VIEW; DWG PS217000). 
    TO ADJUST VERTICAL HEIGHT OF FLOOR STAND FEET, LOOSEN, ADJUST AND TIGHTEN THE NUTS 
    AND 
JAM NUT SHOWN IN (FOOT DETAIL A & B; ON DWG PS217000). FLOOR STAND MUST BE LEVEL 
    AND 
ALL FEET MUST BE TOUCHING THE FLOOR. ATTACH FLOOR STAND FEET USING 1/2" X 4" RED HEAD 
    T
R
U
BOLTS EXPANSION ANCHORS (FEILD SUPPLIED) (2) PER FOOT.
5. ROLL THE STS2 ONTO THE FLOOR STAND SO THAT THE TABS ON THE (REAR UPPER STS2 BRACKET) 
    FIT 
INTO THE SLOTS ON THE (REAR LOWER STS2 BRACKET). TABS TO EXTEND AT LEAST 1/2" THROUGH 
    FLOOR 
STAND BRACKET (FIG. 2, DWG PS217002). 
6. INSTALL 
THE LOWER FRONT BRACKETS (FIG 1, DETAIL A; DWG PS217002). ATTACH BRACKET TO STS2 
    USING 
M10-1.50X30mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 
    31 FT-LBS. 
ATTACH BRACKET TO FLOOR STAND USING M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, 
    AND 
FLAT WASHER AND TORQUE TO 53 FT-LBS
NUT
JAM NUT
NUT
HEIGHT TABLE
P/N OF FLOOR 
STAND:
H
E
IG
H
T
HEIGHT MAX:
H
EIGHT MIN:
523409G1
1
8
.0
"
1
9
.2
5
"
1
6
.7
5
"
523410G1
2
4
.0
"
2
5
.2
5
"
2
2
.7
5
"
523411G1
3
0
.0
"
3
1
.2
5
"
2
8
.7
5
"
523412G1
36.0"
3
7.25"
3
4.75"
6" TYP.
HARDWARE TORQUE 
CHART
1.0" NUT
320 FT - LBS
M8 - 1.25
16FT - LBS
M10 
1.5
31 FT - LBS
M12 - 1.75
5
3
 F
T
 -
L
B
S
PS217000 Rev
. 0