10.2 Manual Transfer / Preferred Source Selection
The Source Transfer option (Source Xfers) in the touch screen menu allows you to select a preferred 
source. Transfers are only permitted when the voltage and current are within their proper operating 
range and the sources are synchronized on units without Optimized Transfer. Units with the 
Optimized Transfer option do not require the sources to be synchronized to make a manual transfer. 
The Source Transfer screen indicates the synchronization between the two sources, while the voltage 
and frequency are displayed on the Mimic. SeFigure 46. Transfer is inhibited if the deviation 
exceeds the parameter set in the Source Set Points. See User Settings on page 89
If your system contains the LED front panel instead of the LCD touch screen, refer to 14.2.2 - 
Figure 46 Source transfer screen
NOTE
If one source will be de-energized for an extended period (hours or days), set the unit to bypass 
mode for the remaining source. Without using bypass, if a failure occurs in the switch 
components for remaining source, the Liebert STS2 does not have a second source to switch to 
and the load would not receive power. See Maintenance Bypass on page 67 for bypass 
instructions.