Operating Instructions for the Touch Screen Interface
68
Figure 47 Gate board viewing slot locations
If the Color Graphical Display is not available, you can still use the following bypass procedures, 
ignore the steps to check the display and check the LEDs.
If your system contains the LED display, see 14.2.3 - Maintenance Bypass.
GREEN LEDS ON THE 
GATE DRIVER BOARD 
ARE VIEWABLE 
THROUGH THIS SLOT 
INDICATE THAT THE 
STS IS ON SOURCE 1
GREEN LEDS ON THE 
GATE DRIVER BOARD 
ARE VIEWABLE THROUGH 
THIS SLOT INDICATE THAT 
THE STS IS ON SOURCE 1
Viewing Slot for 
the Source 1 
Gate Drive Board 
Touch Screen
GREEN LEDS ON THE 
GATE DRIVER BOARD ARE 
VIEWABLE THROUGH THIS 
SLOT INDICATE THAT THE 
STS IS ON SOURCE 2
Viewing Slot for 
the Source 2 
Gate Drive 
Board