Brocade ICX 6650 Hardware Installation Guide
53-1002599-01
Environmental considerations
A
Environmental considerations
 lists the acceptable environmental ranges for both operating and nonoperating (such as 
during transportation or storage) conditions.
Cooling system and fans
Fans cool the CPU, main memory, and voltage regulators. For Brocade ICX 6650 switches, the fans 
use either:
An exhaust airflow which moves air from front to back. See 
. Devices with exhaust 
airflow are labeled with a green arrow with “E.” See 
.
An intake airflow which moves air from back to front. See 
. Devices with intake airflow 
are labeled with an orange arrow with “I.” See 
.
CAUTION
Be sure that the airflow direction of the power supply unit matches that of the installed fan tray. 
The power supplies and fan trays are clearly labeled with either a green arrow with an “E” for 
exhaust, or an orange arrow with an “I” for intake.
TABLE 4
Environmental requirements
Condition
Acceptable during operation
Acceptable during non-operation
Ambient 
Temperature
0º to 40ºC (32º to 104ºF)
-25º to 70ºC (-23º to 158ºF)
Humidity
10% to 95% RH non-condensing, at 
40ºC (104ºF)
5% to 80% RH non-condensing, at 70ºC 
(158ºF)
Altitude
0 to 3 km (9,842 feet) above sea level
0 to 12 km (39,370 feet) above sea level
Shock
20 G, 6 ms, half-sine wave
33 G, 11 ms, half-sine wave, 3/eg Axis
Vibration
0.5 G sine, 0.4 gms random, 5-500 Hz
2.0 G sine, 1.1 gms random, 5-500 Hz
Airflow
Maximum - 90.1 cmh (53 cfm)
Nominal - 59.5 cmh (35 cfm)
N/A
Heat 
dissipation
478 BTU/hr
N/A
Operating 
noise
46.7 dB
N/A