Schneider Electric SR2MAN01 User Manual
Diagnostics
188
SR2MAN01 11/2007
Smart Relay Messages
Description
Here is detailed information on the error messages that are returned by the smart
relay, their possible causes and how to remedy the problem.
relay, their possible causes and how to remedy the problem.
Error Messages
The table below lists the error messages that a smart relay could return. These
messages generally indicate incompatible actions requested by the user.
messages generally indicate incompatible actions requested by the user.
Message
Cause
Corrective action
NO PARAMETER
The user has requested to access the
PARAMETERS option when no parameter is
available (the diagram does not include any
elements with parameters).
PARAMETERS option when no parameter is
available (the diagram does not include any
elements with parameters).
TRANSF.ERR.
A transfer was in progress and the link with the
PC was unexpectedly interrupted.
PC was unexpectedly interrupted.
See the documentation for the
programming software.
programming software.
TRANSFER ERROR: NO
MEMORY
MEMORY
A transfer to the EEPROM was requested and the
EEPROM is not present or incorrectly located.
EEPROM is not present or incorrectly located.
Check the presence and correct
location of the EEPROM.
location of the EEPROM.
TRANSFER ERROR:
CONFIG INCOMPAT
CONFIG INCOMPAT
The user has requested to transfer a program
that does not match the characteristics of the
target smart relay, for example: Clock, analog
input, software version.
that does not match the characteristics of the
target smart relay, for example: Clock, analog
input, software version.
Check the origin of the program to transfer
and choose a program that is compatible
with the appropriate smart relay.
and choose a program that is compatible
with the appropriate smart relay.
TRANSFER ERROR:
VERSION. INCOMPAT
VERSION. INCOMPAT
This error appears if one of the versions of the
smart relay does not correspond to: Firmware,
LD or FBD functions
smart relay does not correspond to: Firmware,
LD or FBD functions
Check the firmware version used.
Outputs are displayed
flashing on the main screen
flashing on the main screen
One or more static outputs have shorted or
overloaded.
overloaded.
Troubleshoot, then stop the smart relay
to end the blinking before selecting
RUN mode again (automatic reset).
to end the blinking before selecting
RUN mode again (automatic reset).