Modbus Plus Network Diagnostic Functions
42
35011984 02/2006
8.2
Scanning the Modbus Plus Network
Procedure for Scanning the Modbus Plus Network
Introduction
When the Diagnostics screen is first displayed, the only node that will appear in the 
list of Modbus Plus Network nodes is the TSXCUSBMBP device itself. A Scan 
function is used to locate other nodes on the network.
Scanning Local 
or Complete 
Network
A scan can be done on either the local Modbus Plus network or the complete 
Modbus Plus network.
z
When scanning the local network, Bridge Plus devices will be shown in the list but 
no scanning will be done on the second network connection on the Bridge Plus.
z
When the complete Modbus Plus network is scanned, every Modbus Plus device 
accessible from the TSXCUSBMBP device will be shown.
Note: The complete network scan is performed as follows:
z
The system sequentially queries each address.
z
The system sends a query to address 1. If a reponse is obtained, the 
information is displayed and the system sends a request to the next address. 
If the device is not connected to the network the system waits for a defined 
timeout period before moving on to the next address.
z
Address polling may be time consuming. For example, depending on the 
network arcitecture (number of devices connected or disconnected) identifying 
247 devices can take up to 12 minutes.
Modbus ID Field
If a node displayed in the scan list has been entered into the routing table used by 
application software to route messages for a specific Modbus ID to that 
Modbus Plus node, the Modbus ID used by the application will be shown in the 
Modbus ID field for that node.