Remote Temperature Sensor 
INSTALLATION INSTRUCTIONS 
APPLICATION 
The T7022 Remote Temperature Sensor is a non-
adjustable thermistor sensor. Its primary use is with the 
T7300 Programmable Commercial Thermostat (only in 
return air) to control heating or cooling equipment. 
NOTE:   The T7022 can also be used with a T7100F, 
provided the proper Q7100 subbase√one 
capable of handling more than one stage of 
heat√is used. 
INSTALLATION 
When Installing this Product... 
1.   Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition. 
2.   Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application. 
3.   Installer must be a trained, experienced service 
technician. 
4.   After installation is complete, check out product 
operation as provided in these instructions. 
CAUTION 
Erratic System Operation Hazard.  
Failure to follow proper wiring practices can 
introduce disruptive electrical interference  
(noise).  
Keep wiring at least one foot away from large 
inductive loads such as motors line starters, 
lighting ballasts, and large power distribution 
panels. 
Shielded cable is required in installations where 
these guidelines cannot be met. 
Ground shield only to grounded controller case. 
CAUTION 
Electrical Shock or Equipment Damage 
Hazard.  
Can shock individuals or short equipment  
circuitry.  
Disconnect power supply before installation. 
IMPORTANT 
All wiring must agree with applicable codes, 
ordinances and regulations. 
Wiring (Fig. 1
Wiring for the T7022 Remote Temperature Sensor can 
be run with class 2 wire in accordance with the National 
Electrical Codes. Conduit and/or shielding are not 
necessary for satisfactory operation, but conduit may be 
required by local codes or practices. 
Q7300
 
T7022
 
M17843 
Fig. 1. Typical wiring diagram. 
Location 
The T7022 Thermostat must be mounted in the return-air 
flow in ducts (see Fig. 2 and 3) or light troffers (see Fig. 4 
and 5). All mounting locations must be where the sensor 
is not affected by heat from the lights or other sources. 
Mounting 
The T7022 can be mounted in a duct with the furnished 
bracket, or in a light troffer as shown in Fig. 4 and 5 with 
two rubber grommets (not supplied) if proper spacing 
is available. Mounting can be directly in the return-air 
passage or in an air-sampling box. The rubber grommets 
can be used to wedge the sensor in slot openings of 
approximately 3/8 in. to 1/2 in. wide. 
When using the mounting bracket, the maximum duct 
insertion length for the T7022 is approximately 2-3/4 in. 
NOTE:   A piece of 3/8 in. diameter conduit can be 
used to extend the sensor further inside a duct 
(see Fig. 3). The use of such an extension can 
increase the maximum insertion length to 
approximately 9-1/2 in. 