Grounded  tools  require  a  three  wire  extension  cord.  Double  insulated
tools can use either a two or three wire extension cord. As the distance
from the supply outlet increases, you must use a heavier gauge exten-
sion cord. Using extension cords with inadequately sized wire causes a
serious  drop  in  voltage,  resulting  in  loss  of  power  and  possible  tool
damage.  Refer  to  the  table  shown  to  determine  the  required  minimum
wire  size.
The smaller the gauge number of the wire, the greater the capacity of the
cord. For example, a 14 gauge cord can carry a higher current than a 16
gauge cord. When using more than one extension cord to make up the
total length, be sure each cord contains at least the minimum wire size
required. If you are using one extension cord for more than one tool, add
the nameplate amperes and use the sum to determine the required mini-
mum wire size.
Guidelines  for  Using  Extension  Cords
•
If  you  are  using  an  extension  cord  outdoors,  be  sure  it  is  marked
with the suffix “W-A” (“W” in Canada) to indicate that it is acceptable
for  outdoor  use.
•
Be sure your extension cord is properly wired and in good electrical
condition. Always  replace  a  damaged  extension  cord  or  have  it
repaired by a qualified person before using it.
•
Protect  your  extension  cords  from  sharp  objects,  excessive  heat
and damp  or  wet  areas.
GROUNDING
EXTENSION CORDS
Grounded  Tools:
Tools  with  Three  Prong  Plugs
Tools  marked  “Grounding  Required”
have  a  three  wire  cord  and  three
prong grounding plug. The plug must
be connected to a properly grounded
outlet (See Figure A). If the tool should
electrically  malfunction  or  break
down,  grounding  provides  a  low  re-
sistance  path  to  carry  electricity
away from the user, reducing the risk
of  electric  shock.
Improperly  connecting  the  grounding  wire  can  result  in  the
risk of electric shock. Check with a qualified electrician if you
are  in  doubt  as  to  whether  the  outlet  is  properly  grounded.
Do  not  modify  the  plug  provided  with  the  tool.  Never  remove
the grounding prong from the plug. Do not use the tool if the
cord  or  plug  is  damaged.  If  damaged,  have  it  repaired  by  a
MILWAUKEE service facility before use. If the plug will not fit
the  outlet,  have  a  proper  outlet  installed  by  a  qualified
electrician.
Nameplate
Amperes
0 - 5
5.1 - 8
8.1 - 12
12.1 - 15
15.1 - 20
Extension Cord Length
25'
16
16
14
12
10
75'
16
14
12
10
10
100'
14
12
10
10
--
150'
12
10
--
--
--
200'
12
--
--
--
--
Recommended  Minimum  Wire  Gauge
for  Extension  Cords*
* Based on limiting the line voltage drop to five
volts at 150% of the rated amperes.
50'
16
16
14
12
10
READ AND SAVE ALL INSTRUCTIONS
FOR FUTURE USE.
The  grounding  prong  in  the  plug  is  connected  through  the  green  wire
inside the cord to the grounding system in the tool. The green wire in the
cord must be the only wire connected to the tool's grounding system and
must never be attached to an electrically “live” terminal.
Your tool must be plugged into an appropriate outlet, properly installed
and  grounded  in  accordance  with  all  codes  and  ordinances.  The  plug
and outlet should look like those in Figure A.
Double  Insulated  Tools:
Tools  with  Two  Prong  Plugs
Tools marked “Double Insulated” do
not require grounding. They have a
special  double  insulation  system
which  satisfies  OSHA  requirements
and  complies  with  the  applicable
standards  of  Underwriters  Labora-
tories,  Inc.,  the  Canadian  Standard
Association and the National Electri-
cal Code. Double Insulated tools may
be used in either of the 120 volt out-
lets shown in Figures B and C.