DeviceNet Network Scanner DVPDNET-SL
 
8  Setup of Slave Mode   
DVPDNET-SL can serve as slave through modifying of the mode by software. As DVPDNET-SL serves as slave, 
the default input / output data length is 8 bytes and max input / output data length is 255 bytes. 
DVPDNET-SL can be set as slave mode in the following method. 
 
1)  Connect the devices according to below figure. PC accesses PLC MPU via RS232 or RS485. 
 
DVP28SV
DVPDNET-SL
DeviceNet Builder
 
2)  Open DeviceNet Builder software, and select “Setup” => “Communication Setting” => “System Channel”, 
and the “Serial Port Setting” dialog box will appear as below. 
 
 
 
3) 
Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud 
rate and communication format. Click on “OK” after configuration is finished.
 
Item 
Function 
Default 
COM Port 
COM port on the PC to be used to communicate 
with DVP-SV 
COM1 
Address 
Communication address of DVP-SV 
01 
Baud rate 
Communication speed between the PC and 
DVP-SV 
9,600 (bps) 
Data Bits 
Parity Even 
Parity 
Stop Bit 
Communication protocol between the PC and 
DVP-SV 
Mode 
Communication mode between the PC and 
DVP-SV 
ASCII 
 
DVP-PLC Operation Manual 