SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
62-0287—03
2
SPECIFICATIONS
General Specifications
Rated Voltage: 20–30 Vac; 50/60 Hz
Power Consumption: 
100 VA for controller and all connected loads (including the 
actuator on models PVL0000AS, PVL4022AS, and 
PVL6436AS)
Controller Only Load: 20 VA maximum; models PUL1012S, 
PUL4024S, PUL6438S, PVL4024NS, and PVL6438NS. 
Controller and Actuator Load: 21 VA maximum; models 
PVL0000AS, PVL4022AS, and PVL6436AS 
External Sensors Power Output: 20 Vdc ±10% @ 75 mA 
maximum
VAV Operating & Storage Temperature Ambient Rating 
(models PVL0000AS, PVL4022AS, PVL4024NS, 
PVL6436AS, and PVL6438NS):
Minimum 32 F (0 C); Maximum 122 F (50 C)
Unitary Operating & Storage Temperature Ambient Rating 
(models PUL1012S, PUL4024S, and PUL6438S):
Minimum -40 F (-40 C); Maximum 150 F (65.5 C)
Relative Humidity: 5% to 95% non-condensing
LED: Provides status for normal operation, controller down-
load process, alarms, manual mode, and error conditions
BEFORE INSTALLATION
The controller is available in eight models (see Table 1).
Review the power, input, and output specifications on page 2 
before installing the controller.
— Hardware driven by  Triac outputs must have a minimum 
current draw, when energized, of 25 mA and a maximum 
current draw of 500 mA.
— Hardware driven by the analog current outputs must have 
a maximum resistance of 550 Ohms, resulting in a 
maximum voltage of 11 volts when driven at 20 mA.
If resistance exceeds 550 Ohms, voltages up to 18 Vdc are 
possible at the analog output terminal.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power supply before beginning wiring or 
making wiring connections to prevent electrical shock 
or equipment damage.
INSTALLATION
The controller must be mounted in a position that allows 
clearance for wiring, servicing, removal, connection of the 
LonWorks® Bus Jack, and access to the Neuron® Service 
Pin.
The controller may be mounted in any orientation.
IMPORTANT
Avoid mounting in areas where acid fumes or other 
deteriorating vapors can attack the metal parts of the 
controller, or in areas where escaping gas or other 
explosive vapors are present. See Fig. 4–Fig. 7 on 
page 4 for mounting dimensions.
For PVL0000AS, PVL4022AS, and PVL6436AS models, the 
actuator is mounted first and then the controller is mounted. 
begin the installation.
Mount Actuator onto Damper Shaft 
(PVL0000AS, PVL4022AS, and PVL6436AS)
PVL0000AS, PVL4022AS, and PVL6436AS controllers 
include the direct-coupled actuator with Declutch mechanism, 
which is shipped hard-wired to the controller.
The actuator mounts directly onto the VAV box damper shaft 
and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and 
90 second timing at 60 Hz. The actuator is suitable for 
mounting onto a 3/8 to 1/2 in. (10 to 13 mm) square or round 
VAV box damper shaft. The minimum VAV box damper shaft 
length is 1-9/16 in. (40 mm).
The two mechanical end-limit set screws control the amount 
of rotation from 12° to 95°. These set screws must be securely 
fastened in place. To ensure tight closing of the damper, the 
shaft adapter has a total rotation stroke of 95° (see Fig. 1).
NOTE: The actuator is shipped with the mechanical end-limit 
set screws set to 95 degrees of rotation. Adjust the 
two set screws closer together to reduce the rotation 
travel. Each “hash mark” indicator on the bracket 
represents approximately 6.5° of rotation per side.
NOTE: The Declutch button, when pressed, allows you to 
rotate the universal shaft adapter (see Fig. 1).
IMPORTANT
Determine the damper rotation and opening angle 
for examples.
 
Fig. 1. Series 60 Floating Actuator.
IMPORTANT
Mount actuator flush with damper housing or add a 
spacer between the actuator mounting surface and 
damper box housing.
UNIVERSAL SHAFT
CLAMPING BOLTS (2)
M23568
UNIVERSAL
SHAFT ADAPTER
MECHANICAL
END LIMIT SET
SCREWS (2)
DECLUTCH