Honeywell PUL1012S User Manual

Page of 8
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
62-0287—03
6
NOTES:
For multiple controllers operating from a single 
transformer, the same side of the transformer sec-
ondary must be connected to the same power 
input terminal in each controller. Controller config-
urations will not necessarily be limited to three 
devices, but the total power draw, including 
accessories, cannot exceed 100 VA when pow-
ered by the same transformer (U.S. only). For 
power and wiring recommendations, see “Wiring” 
on page 5 The earth ground terminal (terminal 3) 
must be connected to a verified earth ground for 
each controller in the group (see Fig. 12 on 
All loads on the controller must be powered by the 
same transformer that powers the controller itself. 
A controller can use separate transformers for 
controller power and output power.
Keep the earth ground connection (terminal 3) 
wire run as short as possible.
Do not connect the universal input COM 
terminals, analog output COM terminals or the 
digital input/output COM terminals to earth 
ground. Refer to Fig. 10–Fig. 12 for wiring 
examples.
The 24 Vac power from an energy limited Class II power 
source must be provided to the controller. To conform to Class 
II restrictions (U.S. only), the transformer must not be larger 
than 100 VA. 
Fig. 10 depicts a single controller using one transformer.
IMPORTANT
Power must be off prior to connecting to or removing 
connections from the 24 Vac power (24 Vac/24 Vac 
COM), earth ground (EGND), and 20 Vdc power (20 
Vdc) terminals..
IMPORTANT
Use the heaviest gauge wire available, up to 
14 AWG (2.0 sq mm), with a minimum of 18 AWG 
(1.0 sq mm), for all power and earth ground wiring.
Screw-type terminal blocks are designed to accept 
up to one 14 AWG (2.0 sq mm) conductor or up to 
two 18 AWG (1.0 sq mm) conductors. More than two 
wires that are 18 AWG (2.0 sq mm) can be con-
nected with a wire nut. Include a pigtail with this wire 
group and attach the pigtail to the terminal block.
IMPORTANT
If the controller is used on Heating and Cooling 
Equipment (UL 1995, U.S. only) and the 
transformer primary power is more than 150 volts, 
connect terminal 2, (the 24 Vac common [24 VAC 
COM] terminal) to earth ground (see Fig. 11). For 
these applications, only one controller can be 
powered by each transformer.
NOTES:
Unswitched 24 Vac power wiring can be run in the 
same conduit as the L
ON
W
ORKS
® cable.
Maintain at least a 3 in. (7.6 cm) separation 
between Triac outputs and L
ON
W
ORKS
® wiring 
throughout the installation.
Fig. 10. Power wiring details for one controller 
per transformer.
Fig. 11. Transformer power wiring details for one 
controller used in UL 1995 equipment (U.S. only).
More than one controller can be powered by a single 
transformer. Fig. 12 shows power wiring details for multiple 
controllers.
NOTE: Controller configurations are not necessarily limited 
to three devices, but the total power draw, including 
accessories, cannot exceed 100 VA when powered 
by the same transformer (U.S. only). For power 
wiring recommendations, see “Wiring” on page 5.
CONNECT POWER TO  
TERMINALS 1 AND 2 
EARTH 
GROUND 
(TERMINAL 3) 
TRANSFORMER 
OUTPUT 
DEVICE 
POWER 
M23557A
Δ
1 2 3 4 5 6 7 8 
2 3 4 5 6 7 8  0 
1  1 1 1 1 1 1 1  2 
1 2 3 4 5 6 7 8  0 
2 2 
2 2 2 2 2 2  3 
1 2 3 4 5 6 7 8  0 
3 3 
3 3 
3 4 
 
COM 
24 VAC 
M23558A
EARTH 
GROUND 
(TERMINAL 3) 
TRANSFORMER 
OUTPUT 
DEVICE 
POWER 
Δ
1 2 3 4 5 6 7 8 
2 3 4 5 6 7 8  0 
1  1 1 1 1 1 1 1  2 
1 2 3 4 5 6 7 8  0 
2 2 
2 2 2 2 2 2  3 
1 2 3 4 5 6 7 8  0 
3  3 
3 3 
3 3 
3 4 
 
EARTH 
GROUND 
LINE VOLTAGE 
GREATER 
THAN 150 VAC 
IF THE CONTROLLER IS USED IN UL 1995 EQUIPMENT AND THE  
PRIMARY POWER IS MORE THAN 150 VOLTS, GROUND 24 VAC COM  
SIDE OF TRANSFORMER SECONDARY. 
COM 
24 VAC 
CONNECT POWER TO  
TERMINALS 1 AND 2