Honeywell PVL4022AS User Manual

Page of 8
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
5
62-0287—03
Panel Mounting
The controller enclosure is constructed of a plastic base plate 
and a plastic factory-snap-on cover. 
NOTE: The controller is designed so that the cover does not 
need to be removed from the base plate for either 
mounting or wiring.
The controller mounts using four screws inserted through the 
corners of the base plate. Fasten securely with four No. 6 or 
No. 8 machine or sheet metal screws.
The controller can be mounted in any orientation. Ventilation 
openings are designed into the cover to allow proper heat 
dissipation, regardless of the mounting orientation.
DIN Rail Mounting (PUL1012S, PUL4024S, 
PUL6438S, PVL4024NS, and PVL6438NS)
To mount  the PUL1012S, PUL4024S, PUL6438S, 
PVL4024NS, or PVL6438NS controller on a DIN rail [standard 
EN50022; 1-3/8 in. x 9/32 in. (7.5 mm x 35 mm)], refer to 
Fig. 8 and perform the following steps:
1. Holding the controller with its top tilted in towards the 
DIN rail, hook the two top tabs on the back of the con-
troller onto the top of the DIN rail.
2. Push down and in to snap the two bottom flex connec-
tors of the controller onto the DIN rail.
Fig. 8. Controller DIN rail mounting (models PUL1012S, 
PUL4024S, PUL6438S, PVL4024NS, and PVL6438NS).
IMPORTANT
To remove the controller from the DIN rail, perform the 
following:
1. Push straight up from the bottom to release the top 
tabs.
2. Rotate the top of the controller out towards you and 
pull the controller down and away from the DIN rail to 
release the bottom flex connectors.
Piping (PVL0000AS, PVL4022AS, 
PVL4024NS, PVL6436AS, and PVL6438NS)
Air flow Pickup
For PVL0000AS, PVL4022AS, PVL4024NS, PVL6436AS, and 
PVL6438NS, connect the air flow pickup to the two restrictor 
ports on the controller (see Fig. 9).
NOTES:
Use 1/4 inch (6 mm) outside diameter, with a 
0.040 in. (1 mm) wall thickness, plenum-rated 
1219 FR (94V-2) tubing.
Always use a fresh cut on the end of the tubing 
that connects to the air flow pickups and the 
restrictor ports on the controller.
Connect the high pressure or upstream tube to the plastic 
restrictor port labeled (
+
), and the low pressure or 
downstream tube to the restrictor port labeled (
-
). See labeling 
in Fig. 9. When twin tubing is used from the pickup, split the 
pickup tubing a short length to accommodate the connections.
NOTES:
If controllers are mounted in unusually dusty or 
dirty environments, an inline, 5-micron disposable 
air filter (use 5-micron filters compatible with 
pneumatic controls) is recommended for the high 
pressure line (marked as 
+
) connected to the air 
flow pickup.
The tubing from the air flow pickup to the control-
ler should not exceed three feet (0.914 m). Any 
length greater than this will degrade the flow 
sensing accuracy.
Use caution when removing tubing from a con-
nector. Always pull straight away from the con-
nector or use diagonal cutters to cut the edge of 
the tubing attached to the connector. Never 
remove by pulling at an angle.
Fig. 9. Air flow pickup connections (PVL0000AS, 
PVL4022AS, PVL4024NS, PVL6436AS, and PVL6438NS).
Wiring
All wiring must comply with applicable electrical codes and 
ordinances, or as specified on installation wiring diagrams. 
Controller wiring is terminated to the screw terminal blocks 
located on the top and the bottom of the device.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power supply before beginning wiring or 
making wiring connections, to prevent electrical shock 
or equipment damage.
DIN RAIL
TOP TABS
BOTTOM FLEX
CONNECTORS
M16815
M23556A
AIR FLOW 
PICKUP 
Δ
1 2 3 4 5 6 7 8 
2 3 4 5 6 7 8  0 
1  1 1 1 1 1 1 1  2 
1 2 3 4 5 6 7 8  0 
2 2 
2 2 2 2 2 2  3 
1 2 3 4 5 6 7 8  0 
3 3 
3 3 
3 4 
RESTRICTOR 
PORT 
RESTRICTOR 
PORT 
CONNECTOR 
TUBING