Bentley 2006 User Manual

Page of 702
 
 
Section 3 
3-15
 
 
any of the radial axes. The values printed for the TRACK 1.0 
output are: 
 
P0 
=  Maximum purely axial load carrying capacity of the 
column (zero moment). 
Pnmax 
=  Maximum allowable axial load on the column 
(Section 10.3.5 of ACI 318). 
P-bal 
=  Axial load capacity at balanced strain condition. 
M-bal 
=  Uniaxial moment capacity at balanced strain condition. 
e-bal 
=  M-bal / P-bal = Eccentricity at balanced strain 
condition. 
M0 = 
Moment 
capacity 
at zero axial load. 
P-tens 
=  Maximum permissible tensile load on the column. 
Des. Pn  =  Pu/PHI where PHI is the Strength Reduction Factor 
and Pu is the axial load for the critical load case. 
Des. Mn  =  Mu*MMAG/PHI where PHI is the Strength Reduction 
Factor and Mu is the bending moment for the 
appropriate axis for the critical load case. For circular 
columns, 
 
 
u
uy
M
M
M
=
+
2
2
uz
 
e/h 
=  (Mn/Pn)/h  where h is the length of the column. 
 
Example for column design per the ACI 318-2002 code 
 
UNIT KIP INCH 
START CONCRETE DESIGN 
CODE ACI 2002 
 
or 
 
CODE ACI 
FYMAIN 58 ALL 
MAXMAIN 10 ALL 
CLB 2.5 ALL