Carrier 50KQL-1PD User Manual

Page of 36
29
REMOTE-MOUNTED THERMOSTAT WITH COMPLETE C CONTROLLER
COMPLETE
C
CONTROL
BR
CR
CAP
PB
GROUND
TRANSFORMER
BRN
YEL
Y
W
O
G
R
C
AL1
AL2
A
P1
ALARM
RELAY
SEE
NOTE 6
JW1
WV
COMPRESSOR
COOLING
FAN
24 VAC
COMMON
ALARM
CLASS 1 WIRING
REQUIRED INSIDE
CONTROL BOX
Y
O
G
R
C
L
CLASS 1 OR 2
WIRING ACCEPTABLE
OUTSIDE
CONTROL BOX
TYPICAL HEAT PUMP T-STAT
SEE NOTE 5
BRN
YEL
BLU
R
Y
JW3
FP1
JW2
FP2
SEE
NOTE 4
COMPR.
RELAY
STATUS
LED
G
COMPLETE C
MICRO-
PROCESSOR
CONTROL
LOGIC
CO
DIP SWITCH
OFF ON
PM: DISABLED/
ENABLED
STAGE 2: 2/1
NOT USED
NOT USED
FP1/FP2
FAULTS: 3/1
1
2
3
4
5
C
TEST PINS
YEL
HP
LOC
FP1
FP2
RV
CO12
P2
24V
DC
EH1
EH2
P3
HP
LOC
FP1
FP2
RVS
CO
SEE
NOTE 4
RED
RED
BLU
BRN
GRY
GRY
VIO
VIO
BRN
ORG
NOT USED
1
2
3
4
5
6
7
8
9
10
RED
(220V)
ORG (240V)
CB
BLK TRANS
24V
SEE
NOTE 7
BR
BRG
CCG
SEE
NOTE 7
CC
YEL
BRN
1
0
CR
BRN
BRN
GRY
YEL
BR
DM
BRN
YEL
ORG
YEL
1
0
BLK
ORG
230V
24V
TRANS
CB*
POWER SUPPLY
REFER TO DATA PLATE
USE COPPER CONDUCTORS ONLY.
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
GROUND
L2
L1
OPTIONAL
CORD
CONNECTION
RED
NEUTRAL ON 265V
SYSTEMS
L2 (ribbed)
GROUND
L1 (plain)
PB
1
2
H
C
F
CAP
RED
RED
6
8
2
4
BLK
BLK
R
S
C
CR
BLU
COMPRESSOR
BRN
YEL
BLK
2
1
BM
B (HIGH)
A (LOW)
RED
BLK
FSS 1
2
BLK
BR
NO
COM
115
208
230
265
WHT
RED
ORG
BRN
LEAD COLOR
VOLTAGE
TRANSFORMER PRIMARY
LEAD COLORS
SEE
NOTE 3
BLOWER MOTOR WIRING
UNIT SIZE
POLE A
POLE B
07
5
3
09
5
4
12
4
3
15
4
3
19
4
3
AL
— Alarm Relay Contacts
BM
— Blower Motor
BR
— Blower Relay
CAP
— Capacitor
CB
— Circuit Breaker
CO
— Sensor, Condensate Overflow
CR
— Compressor Relay
DM
— Damper Motor
FP1
— Sensor, Water Coil Freeze Protection
FP2
— Sensor, Air Coil Freeze Protection
FSS
— Fan Speed Switch
HP
— High-Pressure Switch
JW1
— Jumper Wire for Alarm
LOC
— Loss of Charge Pressure Switch
PB
— Power Terminal Block
PBS
— Push Button Switch
PM
— Performance Monitor
RVS
— Reversing Valve Solenoid
TRANS — Transformer
WV
— Water Valve
----------
Field Line Voltage Wiring
Field Low-Voltage Wiring
LEGEND
Printed Circuit Trace
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lock
>>
*Optional wiring.
NOTES:
1. Compressor and blower motor thermally protected
internally.
2. All wiring to the unit must comply with local codes.
3. Transformer is wired to 115-V (WHT) lead for 115/
1/60 units, 265-V (BRN) lead for 265/1/60 units or
208-V (RED) lead for 208/1/60 units.
For 203/1/60 switch RED and ORG leads at L1
and insulate RED lead.
Transformer is energy limiting or may have circuit
breaker.
4. FP1 thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions, cut
JW3 jumper.
5. Typical heat pump thermostat wiring shown. Refer
to thermostat Installation Instructions for wiring to
the unit.
6. 24-V alarm signal shown. For dry alarm contact,
cut JW1 jumper and dry contact will be available
between AL1 and AL2.
7. Transformer secondary ground via Complete C
board standoffs and screws to control box.
(Ground available from top two standoffs as
shown.)