Hoshizaki DCM-750BWH Supplementary Manual

Page of 69
4
Problem
Possible Cause
Remedy
[5] All components 
run, but no ice is 
produced. (continued)
d) Evaporator
. Defective.
. Replace.
e) Water Supply Line 
(water-cooled model 
only)
. Condenser water 
pressure too low or 
off and high pressure 
control opens and 
closes frequently.
. Check and get 
recommended pressure.
f) Water Regulating Valve 
(water-cooled model 
only)
. Water regulating 
valve set too high or 
clogged (water-cooled 
model only).
. Clean, adjust, or replace. 
2. Low Ice Production
Problem
Possible Cause
Remedy
[] Low ice production.
a)Evaporator
. Dirty or defective.
. Clean or replace. 
b)Bin Control
. Erratic, sticking, 
defective.
. Clean or replace.
c) Drain Valve
. Leaking water.
. Clean or replace.
d)Expansion Valve
. Bulb loose.
. Secure bulb.
. Operating erratically.
. Check and replace.
e)Refrigerant Charge
. Low charge.
. See "V.B. Service for 
Refrigerant Lines."
. Overcharge.
. See "V.B. Service for 
Refrigerant Lines."
f) Refrigerant Line
. Refrigerant line or 
component restricted.
. Repair/replace the 
clogged line/component 
and replace the drier.
g)High-Side Pressure 
Too High
. Dirty air filter or 
condenser. 
. Clean.
. Ambient (or 
condenser) water 
temperature too warm. 
. Reduce temperature.
3. Fan motor slow rpm.
3. See "3. [] a) Fan Motor."
4. Fan motor capacitor.
4. Check and replace.
5. Condenser water 
pressure too low or off 
(water-cooled model 
only).
5. Check and get 
recommended pressure.
6. Water regulating 
valve set too high or 
clogged (water-cooled 
model only).
6. Clean, adjust, or replace. 
h)Compressor
. Inefficient compressor. . Replace
. Faulty thermal 
protector (overload).
. Replace compressor.
3. Faulty capacitor/
starter.
3. Replace.