Chapter 2
Function Reference — CTR_EvCount
©
 National Instruments Corporation
2-93
NI-DAQ FRM for PC Compatibles
10:
SOURCE5 used as timebase if 1 
 ctr 
 5 or SOURCE 10 used as timebase 
if 6
ctr 
 10.
11:
GATE 1 used as timebase if 1 
 ctr 
 5 or GATE6 used as timebase 
if 6
ctr
10.
12:
GATE 2 used as timebase if 1 
 ctr 
 5 or GATE7 used as timebase 
if 6
ctr
10.
13:
GATE 3 used as timebase if 1 
 ctr 
 5 or GATE8 used as timebase 
if 6
ctr
10.
14:
GATE 4 used as timebase if 1 
 ctr 
 5 or GATE9 used as timebase 
if 6
ctr
10.
15:
GATE 5 used as timebase if 1 
 ctr 
 5 or GATE10 used as timebase 
if 6
ctr
10.
Set timebase to zero to concatenate counters. Set timebase to 1 through 5 for the counter to 
count one of the five available internal signals. Set timebase to 6 through 15 (except 10 for 
the PC-TIO-10) to provide an external signal to a counter. This external signal is then the 
signal NI-DAQ counts for event counting. 
cont indicates whether counting continues after the counter reaches 65,535 and rolls over to 
zero. cont can be either zero or 1. If cont = 0, event counting stops when the counter reaches 
65,535 and rolls over, in which case an overflow condition is registered. If cont = 1,  event 
counting continues when the counter rolls over and no overflow condition is registered. 
cont = 1 is useful when more than one counter is concatenated for event counting.
Using This Function
CTR_EvCount
 configures the specified counter for an event-counting operation. The function 
configures the counter to count up from zero and to use the gating mode, edge mode, output 
type, and polarity as specified by the 
CTR_Config
 call.
Note
Edge gating mode does not operate properly during event counting if cont = 1. 
If 
cont = 1, use level gating modes or no-gating mode.
Applications for 
CTR_EvCount
 are discussed in Event-Counting Applications in Chapter 3, 
Software Overview, of the NI-DAQ User Manual for PC Compatibles.