MTD -ERV 365 User Manual

Page of 56
22 Function of the System
3
 
o
t
 
d
e
t
c
e
n
n
o
c
 
e
b
 
t
s
u
m
 
r
o
s
n
e
s
 
H
R
 
e
h
T
 
the PCB panel in the electronics casing 
on the top of the MTD-ERV 350 by the 
installer.
3.4.6  Underground Geothermal Heat 
Exchanger*
As an option, the ventilation system can also be 
equipped with a geothermal heat exchanger.
The  geothermal  heat  exchanger  is  an  addition-
al underground air duct at a depth of at least 1 
metre and with a length of 20 to 40 metres that 
forms  part  of  the  ventilation  system.  The  geo-
thermal heat exchanger allows the outside air to 
be  admitted  to  the  house  under  ground  instead 
of above ground. The heat of the soil is thereby 
given off to the outside air as it fl ows through the 
geothermal heat exchanger.
The geothermal heat exchanger is thus an out-
standing solution both in winter and in summer. 
In frosty weather, the outside air can be heated 
by the underground geothermal heat exchanger 
before it enters the house via the MTD-ERV 350. 
During hot weather in the summer, on the other 
hand,  the  outside  air  can  be  cooled  by  the  un-
derground  geothermal  heat  exchanger  before  it 
enters the house via the MTD-ERV 350.
The  geothermal  heat  exchanger  functions  au-
tomatically.  A  temperature  sensor  installed  any-
where  on  the  outside  of  the  house  measures 
the  temperature  of  the  outside  air.  As  soon  as 
the  temperature  of  the  outside  air  is  between  0 
and 15 
o
C in winter months and between 10 and 
25
o
C  in  summer  months,  the  geothermal  heat 
exchanger is activated to allow the outside air to 
fl ow through the heat exchanger. The user can-
not infl uence the automatic geothermal heat ex-
changer control system. The installer simply has 
to indicate whether or not a geothermal heat ex-
changer has been integrated into the ventilation 
system  in  menu  P60  of  the  CC  Ease  operating 
unit  during  installation  of  the  MTD-ERV 350  (for 
further information, see section 4.4). The installer 
can modify the automatic control of the geother-
mal  heat  exchanger  to  a  slight  extent  in  menu 
P61 at the CC Ease operating unit, if necessary.
e
h
t
d
n
a
r
e
g
n
a
h
c
x
e
t
a
e
h
l
a
m
r
e
h
t
o
e
g
e
h
T  
corresponding temperature sensor must
be connected to the PCB panel (extend-
ed version) of the MTD-ERV 350 by the 
installer.
3.4.7 Chimney Sweep Control
Apart from the chimney sweep control set as
standard in the software, an additional unit can
be connected to the PCB panel (extended ver-
sion) of the MTD-ERV 350 as an option that can
switch off the fans of the MTD-ERV 350 via a float-
ing contact.
By means of a pressure sensor installed in the
room in which the hearth to be monitored is in-
stalled, the unit measures the pressure in the
room with the hearth. The pressure in the room
in which the hearth is installed and the adjacent
rooms must not exceed - 4 Pa so that fumes and
smoke cannot enter the house. At a pressure
higher than - 4 Pa, the fans of the MTD-ERV350
are switched off. Malfunction code "E4" appears
on the display. In this case, please contact the
installation company that installed the pressure
sensor and/or the heating. There is probably a
problem with the discharge of the fumes from the
hearth.
-
d
n
o
p
s
e
r
r
o
c
 
e
h
t
 
d
n
a
 
t
i
n
u
 l
a
n
o
i
t
i
d
d
a
 
e
h
T
 
ing pressure sensor do not belong to the 
standard scope of supply of the MTD-
ERV 350.
-
d
n
o
p
s
e
r
r
o
c
 
e
h
t
 
d
n
a
 
t
i
n
u
 l
a
n
o
i
t
i
d
d
a
 
e
h
T
 
ing pressure sensor must be connected 
to the PCB panel (extended version) of 
the MTD-ERV 350 by the installer.             
The installer cannot infl uence the automatic chim-
ney sweep control system. It reacts to settings at 
the PCB panel (extended version) stored in the 
software.  The  installer  simply  has  to  indicate 
whether or not a chimney sweep control system 
has been integrated into the ventilation system in 
menu P50 of the CC Ease operating unit during 
installation of the MTD-ERV 350 (for further infor-
mation, see section 4.4).