Greenheck Fan SSSMD-201 User Manual

Page of 7
Pressure Drop Data 
SSSMD-201
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All 
data has been corrected to represent standard air at a density of .075 lb/ft
3
 (1.201 kg/m
3
).
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an 
analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC 
system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations 
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper. 
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than 
Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high 
entrance and exit losses due to the sudden changes of area in the system.
5D
6D
5D
D
4 (W) (H)
3.14