Kelvinator KCGM9FW User Manual

Page of 11
•  R
temperature: ‐45~45 C  
ange of set 
(‐40~120 F) 
•  Temperature sensor: NTC, double sensor. 
•  Output contact capacity for compressor: N.O. 
20A/250V~; 50/60Hz. The inrush current for 
compressor control may be 20A instead of 8A 
during the period of 1s at start. (applicable to 1 H.P. 
compressor if more connected to AC contactor) 
•  Output contact capacity for Evap. Fan: N.O. 
20a/250V~; 50/60Hz. 
•  Main controller panel dimension 78
X
35
X
76mm. 
Mounting dimension: 71:29mm 
Indicator 
•  Refrigerant: When the refrigerant LED is on, the 
compressor is working. 
•  Constant temperature: When the refrigerant LED is 
off, the compressor has stopped. 
•  Delay: When the refrigerant LED flashes, the 
compressor stops. 
•  Defrost: When the defrost LED is on, the 
compressor and fan stop and the heater works. 
•  Evaporator fan: When the fan LED is on, the fan is 
working. 
Front Panel Operation  
•  Set temperature: Press  button, the set 
temperature is displayed; Press or button to modify 
and store the displayed value, press 
 button to 
exit the adjustment and display the cold‐room 
temperature. 
•  Manual start/stop defrost: Press   button and 
hold for 6 seconds to defrost or stop defrost.  
•  Display the evaporator temperature: Press   
button and hold for 6 seconds. The evaporator 
temperature will be displayed. After 10 seconds, the 
cold‐room temperature is resumed to be displayed. 
Parameter Setup 
•  Indication for setting parameter: The parameter can 
be adjusted only after correct PA has been entered. 
All parameters can only be checked, not adjusted; 
however, it is available for temperature controlling. 
•  Setting Parameter: Press   for 6 seconds. Start 
parameter menu and PA (menu password) flashing. 
Enter the password by pressing
 or 
. Press
 
again to choose the parameter. Press 
 or 
  
then the parameter can be displayed and adjusted. 
After the adjustment, if no button has been pressed 
after 30 seconds, the system will restore the new 
parameter and go back to normal operations. 
•  Changing menu password (CPA): The CPA can be 
checked or changed only after the correct menu 
password has been entered. When it shows CPA, 
press 
 or 
 then the present password is 
displayed and can be changed to a new password. 
Press 
  to confirm the new password. (Please 
memorize the new password or you can never 
adjust other parameters.) 
•  The factory default resumption: Press   button for 
1 second and then press 
 button simultaneously 
for 6 seconds. The indicator will flash and then all 
parameters will be restored to back to the factory 
defaults. After 10 seconds, it will return to normal 
operation. 
Parameter details 
•  Temperature controlling: After turning on for the 
delay time (e4), the compressor starts operating 
when cold‐room temperature   (set temperature 
+hysteresis), and will off when cold‐room 
temperature   set temperature. To protect the 
compressor it can be re‐started, unless the time 
when the compressor stops every time is longer 
than the delay time (E4). 
•  Evaporator fan operating function: 
F5 is set “00”, parallel with compressor. 
F5 is set “01”, continuous running (except defrost). 
•  Electric heater defrost: evaporator sensor 
temperature < defrost termination temperature 
(F3), the heater will switch on and the defrost will 
start.  
After a defrost interval, it begins the automatic defrost 
function. e.g.: When the evaporator sensor 
temperature < defrost termination temperature (F3), 
the defrost LED will turn on, the compressor and fan will 
stop, and the heater will start. When the evaporator