Conair MPA User Manual

Page of 86
S
PECIFICATIONS
: MPA  (A
IR
C
OOLED
)
UGH004/0999
microKool Portable Chillers
D
ESCRIPTION
2-7
MODEL
MPA-1.5
MPA-2
MPA-3
MPA-4
MPA-5
MPA-7.5
MPA-11
Performance characteristics
Capacity {tons} *
1.2
1.7
2.7
3.5
4.1
6.9
10.2
Compressor   Hp {kW}
1.5 {1.12} 
2.25 {2.05}
3.25 { 279.7}
4 {2.98}
5 {3.73}
9 {6.71}
12 {8.95}
Pump   Hp (kW)†
0.33 {0.246}
0.50 {0.373}
0.75 {0.559}
1.5 {1.12}
1.5 {1.12}
1.5 {1.12}
1.5 {1.12}
Chilled water flow   gpm {l/min}‡
2.8 {10.6}
4.2 {15.9}
6.4 {24.2}
8.5{32.1}
9.9 {37.5} 
16.6 {62.8}
24.5 {92.7}
Chilled water pressure   psi {bar}§
20 {1.4}
26 {1.8}
34 {2.3}
38 {2.6}
38 {2.6}
37.5 {2.6}
37 {2.5}
Reservoir capacity   gal {l}
10 {37.9}
30 {114}
30 {114}
30{ 114}
30 {114}
30 {114}
40.5 {153}
Number of condenser fans 
1
2
2
2
2
2
4
Condenser fan power   Hp  {kW}   
0.063 {0.047}
0.063 {0.047} 0.063 {0.047}
0.063 {0.047}
0.063 {0.047} 0.50 {0.047}
0.50 {0.047}
Condenser air flow    ft
3
/min {l/min}
1050 {496}
1704 {804}
2420 {1142}
4237 {2000}
4237 {2000}
5300 {2501}
8400 {3964}
Dimensions  inches {mm}
A - Height **
45 {1143}
48 {1129}
48 {1129}
56 {1422}
56 {1422}
70 {1778}
76 {1930}
B - Depth
32 {812}
44 {1118}
44 {1118}
48 {1219}
48 {1219}
48 {1219}
48 {1219}
C - Width
29 {737}
29 {737}
29 {737}
34 {737}
34 {737}
34 {737}
40{1016}
Weight lb {kg}
Shipping weight 
750 {340}
1000 {454}
1000 {454}
1200 {544}
1200 {544}
1400 {635}
1600 {726}
Installed weight 
610 {277}
830 {376}
830 {376}
1030 {467}
1030 {467}
1230 {558}
1430 {649}
Utility Requirements
Water connections  NPT (female) inches
1
1
1
1.5
1.5
1.5
1.5
Process water     inches
1
1
1
1.5
1.5
1.5
1.5
Voltages  running and full load amps
run
full
run
full
run 
full
run
full
run
full
run
full
run
full
208V/3 phase/60hz 
11.7
18.3
16.1
18.6
21.0
27.0
27.8
32.3
31.0 34.5
63.0
69.6
90.8
97.8
230V/3 phase/60hz                         
10.6
16.6
14.6
16.8
19.0
24.4
25.2
29.2
28.0 31.2
57.0
63.0
82.2
88.5
460V/3 phase/60hz
5.3
8.3
7.3
8.4
9.5
12.2
12.6
14.6
14.0 15.6
28.5
31.5
41.1
44.3
575V/3 phase/60hz
4.2
6.6
5.8
6.7
7.6
9.8
10.1
11.7
11.2 12.5
22.8
25.2
32.9
35.4
SPECIFICATION NOTES
*  Based on 50° F (10° C) water temperature (100% water) leaving the chiller, standard pump selections, 95° F (35° C) ambient air conditions.
Consult factory for other conditions.
†  Standard pump selection. Larger pumps available as options.
‡  Based on 50° F water temperature leaving the chiller 60° F (15° C) water temperature returning to the chiller.
§  Pressure at pump discharge.
** Control can be extended upward approximately 11 inches, which may or may not increase the overall height of the unit.
Specifications may change without notice. Check with a Conair representative for the most current information.
Flow  Rate (gpm)
60 HZ PUMP PERFORMANCE CURVES  
Pressure  (psi)