Emerson Fluid Chiller User Manual

Page of 64
4A.3 Temperature Setpoint for Chiller
The temperature setpoint for the chiller should be set by turning the potentiometer. To obtain an 
accurate setpoint, connect a voltmeter (millivolt) to TP1 and TP2. The readout will display tem-
perature in degrees Fahrenheit. Turn the potentiometer to the desired setpoint.
A “well” sensor is factory-piped and wired to accurately measure the temperature of the water 
leaving the chiller. This sensor provides input to the Electronic Hot Gas Bypass Controller. The 
sensor changes electrical resistance in response to temperature changes. To check or troubleshoot 
the sensor, disconnect it from the controller and measure the resistance. Figure 3E shows the 
relationship between temperature and resistance.
Figure 3E Temperature sensor resistance
4A.4 Flow Control
A circuit setter is factory-installed in the supply line and a ball valve is factory-installed in a 
bypass loop. The desired system flow to the load should be set by adjusting the circuit setter to the 
required flow rate. If a flow rate of less than 5 gpm is required, the ball valve should be adjusted 
to keep the overall system flow rate up. If low suction pressures are present, the circuit setter 
should be set to a higher flow, with the bypass valve used to control flow to the load.