Emerson XDCF User Manual

Page of 28
Installation
8
4.3
Mounting Lower Liebert XDCF Module
The lower Liebert XDCF module attaches to the Egenera BladeFrame cabinet with a mounting 
bracket, four bolts and a metal stud.
Before the Liebert XDCF is mounted, the mounting bracket and a two-piece deflector panel must be 
attached to its top surface and insulation must be applied to the left side.
4.3.1 Preparing the Lower Module for Attachment
1. Position the mounting bracket over the two mounting holes. The holes are near the center of the 
top of the Liebert XDCF module (see Figure 7).
2. Use two captive panel fasteners to attach the mounting bracket to the top of the Liebert XDCF 
module. Tighten the fasteners securely, using a screwdriver, either a blade-type or Phillips.
3. Position the top deflector over the two mounting holes along the front edge of the top of the lower 
Liebert XDCF module (see Figure 7). The flanges along the edge should be on the bottom.
4. Use two captive panel fasteners to attach the top deflector to the top of the lower Liebert XDCF 
module.Tighten the fasteners securely, using a screwdriver, either a Phillips or a blade-type.
5. Position the second piece of the top deflector along the front edge of the deflector piece attached in 
Steps 3 and 4matching the mounting slots in the two pieces. The flanges along the edge should 
be on the bottom.
6. Use two captive panel fasteners to connect the deflector pieces. Tighten the fasteners finger-tight, 
leaving them loose enough to slide for good contact with the Egenera BladeFrame cabinet.
Figure 7
Lower Liebert XDCF attachments
Positioning Stud
Mounting bracket and
top deflector
attached
to unit
LEFT
SIDE
FRONT
Captive nuts
for mounting
bracket, 2
Slots in front piece
of deflector permit
proper positioning
FRONT
Holes for attaching
top deflector
RIGHT SIDE